Er27 on a Cool Energy heat pump: Outlet water temperature sensor fault

Short answer

On a Cool Energy heat pump, Er27 means: Outlet water temperature sensor fault. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 3 sources

What it means

On the ecoTech DC Inverter (R32 EVI)

The manual says: Outlet water temperature sensor fault.

On the Inverter range CE-iH (R410A, c.2020)

The manual says: Low Pressure Fault.

When it shows: Low pressure on compressor; not detected during defrost or first 5 min after start (p.21).

On the Pro Range CE-H (fixed-speed)

The manual says: Faulty outlet water temp sensor.

Likely causes:

  • Outlet water temperature sensor faulty.
  • Sensor plug disconnected/oxidised.
  • Controller/PC board faulty.

Is it safe?

On the ecoTech DC Inverter (R32 EVI)

Does the heat pump stop?Yes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

On the Inverter range CE-iH (R410A, c.2020)

Does the heat pump stop?Yes
SeveritySafety lockout
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Resumes 3 min after reset.

Manual reset: Permanently disabled after 3 occurrences within 1 hour.

On the Pro Range CE-H (fixed-speed)

Does the heat pump stop?Yes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

What you can check

On the ecoTech DC Inverter (R32 EVI)

  • Read and note the code shown on the controller display, then contact your installer or service engineer.

On the Inverter range CE-iH (R410A, c.2020)

  • Read and note the code shown on the controller display, then contact your installer or service engineer.
  • Check the heating system pressure gauge reading against the value in your handover documents (manufacturer commissioning values: typically 1-2 bar) and that the filling loop is closed.
  • Check the outdoor unit/air grilles are not blocked by debris, leaves or snow.

On the Pro Range CE-H (fixed-speed)

  • Read and note the code shown on the controller display, then contact your installer or service engineer.

What the engineer will check

On the ecoTech DC Inverter (R32 EVI)

  • Check the named sensor/probe connection at the PCB (loose/oxidised plug).
  • Measure sensor resistance against the manufacturer table and replace if faulty.
  • Check controller/PCB if sensor is good.

Who to ask for: heat pump controls / electrical.

Certification: Electrical competence.

On the Inverter range CE-iH (R410A, c.2020)

  • Check water flow first (high pressure is often caused by low flow).
  • Check refrigerant pressures/temperatures with gauges (F-gas qualified).
  • Check for refrigerant leak or blockage, EEV operation and pressure switches/transducers.

Who to ask for: refrigeration / F-gas heat pump engineer.

Certification: F-gas certification (Category I) for refrigerant circuit work.

On the Pro Range CE-H (fixed-speed)

  • Replace or reconnect/clean sensor.
  • Replace controller/PC board.
  • Check the named sensor/probe connection at the PCB (loose/oxidised plug).
  • Measure sensor resistance against the manufacturer table and replace if faulty.
  • Check controller/PCB if sensor is good.

Who to ask for: heat pump controls / electrical.

Certification: Electrical competence.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026