SolarpunkHomes
Sign inCall us · +44 7510 081687
Solar
Solar · Error codes · SMA Solar Technology AG
3410SMA Solar Technology AG · Sunny Boy Smart Energy

3410 on a SMA Solar Technology AG Sunny Boy Smart Energy: Overvoltage at the DC input. This can destroy the inverter. This message is signalized additionally by rapid flashing of the LEDs

Short answer

On a SMA Solar Technology AG inverter, 3410 means: Overvoltage at the DC input. This can destroy the inverter. This message is signalized additionally by rapid flashing of the LEDs. The inverter stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 24 September 2026 · 1 source

What it means

The manual says: Overvoltage at the DC input. This can destroy the inverter. This message is signalized additionally by rapid flashing of the LEDs.

Part involved: DC overvoltage.

When it shows: Overvoltage at the DC input. This can destroy the inverter. This message is signalized additionally by rapid flashing of the LEDs.

Likely causes:

  • SMA corrective measures: Immediately disconnect the inverter from voltage sources and secure it against being switched on again. Check whether the DC voltage is below the maximum input voltage of the inverter. If the DC voltage is below the maximum input voltage of the inverter, reconnect the DC cables to the inverter. If the DC voltage exceeds the maximum input voltage of the inverter, ensure that the PV array has been correctly rated or contact the installer of the PV array. If this message is repeated frequently, con.

Is it safe?

Switch the inverter off at its isolator and call an engineer.

Does the inverter stop?Yes
SeveritySafety lockout
Engineer needed?Yes

The inverter stops until the fault clears or is reset.

Resetting itself: no.

Manual reset: Reconnect only after DC voltage verified below the maximum input voltage.

What you can check

  • Read the event number and message in the SMA Energy app / Sunny Portal (ennexOS) or the inverter's web interface and note the date/time for your installer. A red LED on the inverter means an event has occurred.
  • SMA states this overvoltage can destroy the inverter and the inverter must be disconnected immediately by a qualified person - call your installer urgently and do not touch the DC isolator or cables.

What the engineer will check

  • Immediately disconnect inverter from all voltage sources; measure DC string voltage against max input voltage; redesign string if above limit; contact SMA Service if inverter damaged.

Who to ask for: MCS PV installer.

Certification: Qualified electrician (BS 7671; MCS-certified PV installer for work on the PV array/DC side).

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 24 September 2026