Heat pumps · Error codes · Worcester Bosch
HPWorcester Bosch

HP on a Worcester Bosch heat pump: Alarm table: Cooling mode low pressure protection (in 1 hour, low pressure is below 0.6 MPa three consecutive times, can be reset automatically) / Troubleshooting table: Low pressure protection (Pe < 0.6) tripped 3 times in one hour

Short answer

On a Worcester Bosch heat pump, HP means: Alarm table: Cooling mode low pressure protection (in 1 hour, low pressure is below 0.6 MPa three consecutive times, can be reset automatically) / Troubleshooting table: Low pressure protection (Pe < 0.6) tripped 3 times in one hour. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 3 sources

What it means

On the Bosch Compress 2000 AWF (R32 all-in-one monobloc)

The manual says: Alarm table: Cooling mode low pressure protection (in 1 hour, low pressure is below 0.6 MPa three consecutive times, can be reset automatically) / Troubleshooting table: Low pressure protection (Pe < 0.6) tripped 3 times in one hour.

Part involved: low pressure protection (cooling).

When it shows: Cooling mode low pressure protection (in 1 hour, low pressure is below 0.6 MPa three consecutive times, can be reset automatically).

Likely causes:

  • See P0.

On the Greenstar Plus Hybrid (air to water heat pump + Worcester boiler)

The manual says: External unit / water flow rate fault; heat pump flow switch fault during self-test (status L).

Part involved: hybrid control module / FW200.

When it shows: External unit / water flow rate fault; heat pump flow switch fault during self-test (status L).

Likely causes:

  • Fault affecting heat pump / water flow interrupted: check LED signals, throughput, filter, flow switch, system.

On the Greenstore ground source heat pump (original, System & Combi)

The manual says: High pressure switch (HP).

Part involved: high pressure switch.

When it shows: High pressure switch (HP).

Likely causes:

  • Insufficient primary flow (pump stopped, valves closed); primary filter blocked; air in primary circuit.

Is it safe?

On the Bosch Compress 2000 AWF (R32 all-in-one monobloc)

Does the heat pump stop?Yes
SeverityFault — clears by itself when the condition goes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: yes.

Manual reset: Manual 13.2: switch the unit off and on again to reset the safety device; if reset fails contact dealer. Manual 11.4 warns repeated resets can cause irreversible damage.

On the Greenstar Plus Hybrid (air to water heat pump + Worcester boiler)

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: no.

Manual reset: Hold Back button on hybrid control module 5 s to restart after fault is rectified (installer).

On the Greenstore ground source heat pump (original, System & Combi)

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: no.

Manual reset: Press Ackn. on the control panel; heat pump restarts within 15 minutes if there is demand. Some causes need a reset button/MCB on the heat pump (engineer).

What you can check

On the Bosch Compress 2000 AWF (R32 all-in-one monobloc)

  • Read and note the full code (and sub-code) shown on the controller and pass it to your installer.
  • Check the outdoor unit is not blocked by leaves, snow, ice or other debris (do not open the casing).
  • Manual 13.2: one off/on restart may be tried; if the code returns, stop and call an engineer - repeated resets can damage the unit.

On the Greenstar Plus Hybrid (air to water heat pump + Worcester boiler)

  • Read and note the full code (and sub-code) shown on the controller and pass it to your installer.
  • Check whether the boiler display also shows a fault (manual: if the boiler shows a fault the heat pump is not faulty) and report both to the engineer.
  • Check the heating system pressure gauge reading (Bosch guidance is typically 1-2 bar when cold); report low pressure to your installer.

On the Greenstore ground source heat pump (original, System & Combi)

  • Read and note the full alarm text and code in brackets shown on the controller and pass it to your installer.
  • Check the heating system pressure gauge reading (Bosch guidance is typically 1-2 bar when cold); report low pressure to your installer.
  • Press the Ackn. button once as the manual describes (manual: no risk in resetting an alarm); contact technical support if the alarm repeats.

What the engineer will check

On the Bosch Compress 2000 AWF (R32 all-in-one monobloc)

  • Follow P0 checks.

Who to ask for: F-gas refrigeration engineer / heat pump installer.

Certification: F-gas certification (Category I) required for refrigerant circuit work; qualified electrician for electrical work.

On the Greenstar Plus Hybrid (air to water heat pump + Worcester boiler)

  • Fault affecting heat pump / water flow interrupted: check LED signals, throughput, filter, flow switch, system.

Who to ask for: heat pump installer / heating engineer.

Certification: None specific for hydraulic checks; MCS-certified installer recommended for system changes.

On the Greenstore ground source heat pump (original, System & Combi)

  • Check pump, valves, filter; vent; increase pump speed.

Who to ask for: heat pump installer / heating engineer.

Certification: None specific for hydraulic checks; MCS-certified installer recommended for system changes.

What you might notice

What owners and engineers report

4 owner and engineer reports mention this.

  • Keeps stopping / cutting out on the Bosch Compress 2000 AWF (R32 all-in-one monobloc): 1 report
  • No heating on the Greenstore ground source heat pump (original, System & Combi): 2 reports
  • Keeps stopping / cutting out on the Greenstore ground source heat pump (original, System & Combi): 1 report

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026