Heat pumps
Heat pumps · Error codes · Worcester Bosch
E9Worcester Bosch · Bosch Compress 2000 AWF (R32 all-in-one monobloc)

E9 on a Worcester Bosch Bosch Compress 2000 AWF: Alarm table: Temperature sensor Th failure / Troubleshooting table: Th suction pipe sensor error

Short answer

On a Worcester Bosch heat pump, E9 means: Alarm table: Temperature sensor Th failure / Troubleshooting table: Th suction pipe sensor error. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Alarm table: Temperature sensor Th failure / Troubleshooting table: Th suction pipe sensor error.

Part involved: Th suction temperature sensor.

When it shows: Temperature sensor Th failure.

Likely causes:

  • Sensor connector loose, wet/water ingress in connector, or sensor faulty (manual: reconnect, dry and seal connector with waterproof adhesive, or replace sensor).

Is it safe?

Does the heat pump stop?Yes
SeverityFault — clears by itself when the condition goes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: yes.

Manual reset: Manual 13.2: switch the unit off and on again to reset the safety device; if reset fails contact dealer. Manual 11.4 warns repeated resets can cause irreversible damage.

What you can check

  • Read and note the full code (and sub-code) shown on the controller and pass it to your installer.
  • Manual 13.2: one off/on restart may be tried; if the code returns, stop and call an engineer - repeated resets can damage the unit.

What the engineer will check

  • Check sensor connector seating and moisture; measure sensor resistance; replace sensor if faulty (inside unit casing - isolate power, wait 10 min for DC bus discharge).

Who to ask for: F-gas refrigeration engineer / heat pump installer.

Certification: F-gas certification (Category I) required for refrigerant circuit work; qualified electrician for electrical work.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026