F06Trianco

F06 on a Trianco heat pump: DC Bus Under voltage

Short answer

On a Trianco heat pump, F06 means: DC Bus Under voltage. The manual does not say whether the heat pump stops. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 3 sources

What it means

On the Activair High Temperature R290 (5/9/15/22kW)

The manual says: DC Bus Under voltage.

Part involved: compressor driver / inverter board.

Likely causes:

  • DC bus voltage below threshold.

On the Activair R290 Indoor (3.2kW wall hung / 5kW floor standing)

The manual says: DC Power Bus Undervoltage.

Part involved: compressor driver / inverter board.

Likely causes:

  • DC bus voltage < DC bus underload-voltage protection value.

On the Activair Pro (AI) R290 6/12/17kW

The manual says: DC Power Bus Undervoltage Fault.

Part involved: compressor driver / inverter board.

Likely causes:

  • DC bus voltage is below the undervoltage protection threshold.

Is it safe?

Does the heat pump stop?Not stated
Engineer needed?Yes

The manual does not say whether the heat pump stops.

What you can check

  • Note the exact code shown on the controller (a photo helps) and report it to your installer or the manufacturer's service line.
  • Check the heat pump's supply breaker/isolator at the consumer unit is on (do not open any casing).

What the engineer will check

On the Activair High Temperature R290 (5/9/15/22kW)

  • Check the voltage between DCP-IN and DCN-IN.
  • if lower than 300V this protection occurs.
  • Check input voltage of R/S/T on driver board.
  • if lower than 210V this protection occurs.
  • If OK, replace compressor driver board.

Who to ask for: heat pump electrical / inverter.

Certification: Electrical competence; manufacturer-trained heat pump engineer.

On the Activair R290 Indoor (3.2kW wall hung / 5kW floor standing)

  • Check the input voltage measurement.

Who to ask for: heat pump electrical / inverter.

Certification: Electrical competence; manufacturer-trained heat pump engineer.

On the Activair Pro (AI) R290 6/12/17kW

  • Check the input voltage measurement.

Who to ask for: heat pump electrical / inverter.

Certification: Electrical competence; manufacturer-trained heat pump engineer.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.