SolarpunkHomes
Sign inCall us · +44 7510 081687
Heat pumps
Heat pumps · Error codes · Technibel S.A.S.
P03Technibel S.A.S. · Technibel PHRIE / PHIE inverter monobloc air-to-water (medium temperature)

P03 on a Technibel S.A.S. Technibel PHRIE / PHIE inverter monobloc air-to-water: Abnormal discharge temperature: TD at or above 111 C (095-197) / 115 C (257/307); alarm after 4 consecutive pre-trips

Short answer

On a Technibel S.A.S. heat pump, P03 means: Abnormal discharge temperature: TD at or above 111 C (095-197) / 115 C (257/307); alarm after 4 consecutive pre-trips. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Abnormal discharge temperature: TD at or above 111 C (095-197) / 115 C (257/307); alarm after 4 consecutive pre-trips.

Likely causes:

  • Refrigerant leak.
  • Electronic expansion valve.
  • TD sensor.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Manual reset: fault memorised by A2 board; reset by A2 RESET button (5 s), setting system control to OFF, or switching off power (power-off recommended for E15/E16/E20/L02/L08/L09/L10/L13/F29/F31).

What you can check

  • Note the code/LED pattern and the model from the rating plate, then contact a heat pump/refrigeration engineer.
  • Check the heat pump's breaker/isolator at the consumer unit is on.

What the engineer will check

  • Check refrigerant circuit for leaks.
  • Check EEV.
  • Check TD/S5.

Who to ask for: refrigeration / heat pump engineer.

Certification: F-gas certification (refrigerant circuit work) and electrical competence.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026