Heat pumps · Error codes · Technibel S.A.S.
F02Technibel S.A.S. · Technibel PHRIE / PHIE inverter monobloc air-to-water (medium temperature)

F02 on a Technibel S.A.S. Technibel PHRIE / PHIE inverter monobloc air-to-water: Abnormal pressure detected in plate exchanger by E2P/B1 pressure sensor (value out of range)

Short answer

On a Technibel S.A.S. heat pump, F02 means: Abnormal pressure detected in plate exchanger by E2P/B1 pressure sensor (value out of range). The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Abnormal pressure detected in plate exchanger by E2P/B1 pressure sensor (value out of range).

Likely causes:

  • Pressure sensor or A2 board fault.
  • Actual abnormal circuit pressure.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — clears by itself when the condition goes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Automatic stop; if the fault lasts <30 min it clears automatically, if >30 min it is memorised (AL LED steady) and needs manual reset (A2 RESET button 5 s, system control OFF, or power off).

What you can check

  • Note the code/LED pattern and the model from the rating plate, then contact a heat pump/refrigeration engineer.
  • Check the heat pump's breaker/isolator at the consumer unit is on.

What the engineer will check

  • Check refrigerant circuit pressure.
  • Check E2P-A2 connection and JTP bridge (2-3).
  • Measure 24 V DC on E2P connector pins 1/3 (20-26 V): OK = sensor faulty, wrong = A2 faulty.

Who to ask for: refrigeration / heat pump engineer.

Certification: Electrical competence for work inside the unit.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026