E12Navien · PEM750

E12 on a Navien PEM750: LP protection (LP switch is open)

Short answer

On a Navien heat pump, E12 means: LP protection (LP switch is open). The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 24 September 2026 · 1 source

What it means

The manual says: LP protection (LP switch is open).

Part involved: compressor / refrigerant circuit.

Likely causes:

  • Measure suction pressure running; check EEV step, discharge pressure, water temperatures; check for leaks; recharge to nameplate. Restart manually if it fails more than 3 times in 30 min.

Is it safe?

Does the heat pump stop?Yes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: unknown.

What you can check

  • Note the code shown on the controller and the model number on the unit's rating label before contacting your installer.
  • Check that the heat pump's isolator and consumer-unit breaker are on; do not open any casing.

What the engineer will check

  • Record high/low pressures, discharge/suction temperatures and EEV steps with the unit running.
  • Check water-side flow and air-side coil (blocked/frosted fins).
  • Check pressure switches/transducers and wiring.
  • Leak-test the refrigerant circuit and correct the charge (F-gas / flammable-refrigerant competent engineer only).

Who to ask for: Heat pump engineer.

Certification: Heat pump installer competence; F-gas and flammable-refrigerant (R32/R290) handling competence for any refrigerant-circuit work.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 24 September 2026