32 on a Mitsubishi Heavy Industries Air-Conditioning Europe Hydrolution HM gen 1: Sensor fault, condenser out (BT12)

Short answer

On a Mitsubishi Heavy Industries Air-Conditioning Europe heat pump, 32 means: Sensor fault, condenser out (BT12). The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Sensor fault, condenser out (BT12).

Part involved: Sensor fault KF.

Likely causes:

  • Open-circuit or short-circuit on sensor input; sensor does not work.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: no.

Manual reset: yes (switch SF1 off/on per user manual).

What you can check

  • Note the alarm number/text shown on the display. Check the consumer-unit breakers/isolators for the indoor and outdoor units are on. The user manual allows resetting by switching the indoor unit off and on with switch SF1; if the alarm cannot be reset, hold the operating-mode button to select 'Add. heat only' (immersion heating) and contact the installer. Recurring alarms mean an installation fault.

What the engineer will check

  • Indoor-unit checks per HM-T-193 flowchart: check sensors BT12/BT15/BT3, water-side service valves, valves QM31/QN11, strainer, air bleed, circulation pump setting (menu 2.2.5) and relay board AA6; check refrigerant charge/leaks for defrost alarms.

Who to ask for: Heat pump / refrigeration engineer (manufacturer-trained).

Certification: F-gas certification for refrigerant-circuit work; electrical competence (Part P/18th Edition) for PCB/wiring.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.