P6 on a Mitsubishi Electric heat pump: Freezing/Overheating protection operation

Short answer

On a Mitsubishi Electric heat pump, P6 means: Freezing/Overheating protection operation. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 16 sources

What it means

On the Ecodan

The manuals for this range word it in different ways:

  • Freezing/Overheating protection operation.
  • Anti-freeze protection of plate heat exchanger.

Part involved: Plate heat exchanger / TH2 / water flow.

When it shows: Freeze or overheat protection operated at the FTC2 heat exchanger FTC4-FTC6: cooling - TH2 <= -5C for 10 s after 6 min compressor run; defrost - THW2 <= 15C and TH2 <= -16C for 10 s. FTC7: refrigerant temperature drops rapidly in cooling/defrost (TH2 or pressure sensor; depends on plate HEX capacity code).

Likely causes:

  • Reduced water flow; abnormal water temperature; refrigerant circuit condition.
  • 1 Reduced water flow (clogged filter, water leak); 2 Low temperature (low load, inlet water too cold); 3 Defective water pump; 4 Defective outdoor fan control (cooling); 5 Overcharge / leakage or shortage of refrigerant; 6 Defective refrigerant circuit (clogs); 7 Malfunction of linear expansion valve; 8 Malfunction of pressure sensor / incorrect capacity code (FTC7).

On the Ecodan Hydrodan

The manual says: Anti-freeze protection of plate heat exchanger.

Part involved: Plate heat exchanger / TH2 / water flow.

When it shows: FTC4-FTC6: cooling - TH2 <= -5C for 10 s after 6 min compressor run; defrost - THW2 <= 15C and TH2 <= -16C for 10 s. FTC7: refrigerant temperature drops rapidly in cooling/defrost (TH2 or pressure sensor; depends on plate HEX capacity code).

Likely causes:

  • 1 Reduced water flow (clogged filter, water leak); 2 Low temperature (low load, inlet water too cold); 3 Defective water pump; 4 Defective outdoor fan control (cooling); 5 Overcharge / leakage or shortage of refrigerant; 6 Defective refrigerant circuit (clogs); 7 Malfunction of linear expansion valve; 8 Malfunction of pressure sensor / incorrect capacity code (FTC7).

On the Ecodan Puhz Sw Split

The manual says: Freezing/overheating protection is working - overheating protection in heating mode (split outdoor unit).

Part involved: Pressure sensor 63HS / refrigerant charge / water flow at indoor plate HEX.

When it shows: Heating: condensing temperature from 63HS >= Tcond (ambient-dependent, approx. 63C at -18C falling to 50-51C at higher ambients) with compressor frequency <= 25 Hz; not detected during defrost.

Likely causes:

  • 1 Overcharge of refrigerant; 2 Defective refrigerant circuit (clogs); 3 Malfunction of linear expansion valve; 4 Reduced water flow (clogged filter, water leak); 5 High temperature (overload, inlet water too warm); 6 Defective water pump.

On the Ecodan Puhz W Monobloc

The manual says: Freezing/overheating protection is working (plate heat exchanger freeze protection detected by outdoor unit).

Part involved: Plate heat exchanger / water flow / refrigerant charge.

When it shows: Cooling: plate HEX pipe TH6 <= -5C for 10 s, or <= -2C at minimum frequency for 5 min after 6 min running. Heating/defrost (inlet water TH32 <= 15C): TH6 <= -6C for 30 s after 1 min of defrost, or TH6 <= -16C for 10 s during defrost.

Likely causes:

  • Cooling: 1 Reduced water flow (clogged filter, leak); 2 Low temperature (low load, inlet water too cold); 3 Defective water pump; 4 Defective outdoor fan control; 5 Overcharge of refrigerant; 6 Clogged refrigerant circuit; 7 LEV malfunction. Heating: 1 Reduced water flow; 2 Low temperature; 3 Defective water pump; 4 Leakage or shortage of refrigerant; 5 LEV malfunction.

On the Ecodan R290 Puz Wz

The manual says: Freezing/overheating protection is working (plate heat exchanger freeze protection detected by outdoor unit).

Part involved: Plate heat exchanger / water flow / refrigerant charge.

When it shows: Refrigerant saturation temperature (WZ50-80 also plate HEX liquid TH34) below a dynamically calculated threshold for 10 s; OCH880 describes freezing protection (cooling) and overheating protection (heating).

Likely causes:

  • Cooling: 1 Reduced water flow (clogged filter, water leak); 2 Low temperature (low load, inlet water too cold); 3 Defective water pump; 4 Defective outdoor fan control; 5 Leakage or shortage of refrigerant; 6 Defective refrigerant circuit (clogs); 7 Malfunction of LEV. Heating/defrost: 1 Reduced water flow; 2 Low temperature (low load, cold inlet water); 3 Defective water pump; 4 Leakage or shortage of refrigerant; 5 Malfunction of LEV.

On the Ecodan R32 Puz Wm

The manual says: Freezing/overheating protection is working (plate heat exchanger freeze protection detected by outdoor unit).

Part involved: Plate heat exchanger / water flow / refrigerant charge.

When it shows: Plate HEX liquid temperature (TH34) or refrigerant saturation temperature below a dynamically calculated threshold for 10 s.

Likely causes:

  • Cooling: 1 Reduced water flow (clogged filter, water leak); 2 Low temperature (low load, inlet water too cold); 3 Defective water pump; 4 Defective outdoor fan control; 5 Leakage or shortage of refrigerant; 6 Defective refrigerant circuit (clogs); 7 Malfunction of LEV. Heating/defrost: 1 Reduced water flow; 2 Low temperature (low load, cold inlet water); 3 Defective water pump; 4 Leakage or shortage of refrigerant; 5 Malfunction of LEV.

On the Ecodan R32 Zubadan Puz Hwm

The manual says: Freezing/overheating protection is working (plate heat exchanger freeze protection detected by outdoor unit).

Part involved: Plate heat exchanger / water flow / refrigerant charge.

When it shows: Plate HEX liquid temperature (TH34) or refrigerant saturation temperature below a dynamically calculated threshold for 10 s.

Likely causes:

  • Cooling: 1 Reduced water flow (clogged filter, water leak); 2 Low temperature (low load, inlet water too cold); 3 Defective water pump; 4 Defective outdoor fan control; 5 Leakage or shortage of refrigerant; 6 Defective refrigerant circuit (clogs); 7 Malfunction of LEV. Heating/defrost: 1 Reduced water flow; 2 Low temperature (low load, cold inlet water); 3 Defective water pump; 4 Leakage or shortage of refrigerant; 5 Malfunction of LEV.

On the Ecodan Ultra Quiet Puhz W Vaa

The manual says: Freezing/overheating protection is working (plate heat exchanger freeze protection).

Part involved: Plate heat exchanger / water flow / refrigerant charge.

When it shows: Cooling: plate HEX pipe TH6 <= -5C for 10 s, or <= -2C at minimum frequency for 5 min after 6 min running. Heating/defrost (TH34 inlet water <= 15C): TH6 <= -6C for 30 s after 1 min of defrost, or TH6 <= -16C for 10 s during defrost.

Likely causes:

  • Cooling: 1 Reduced water flow (clogged filter, leak); 2 Low temperature (low load, inlet water too cold); 3 Defective water pump; 4 Defective outdoor fan control; 5 Overcharge of refrigerant; 6 Clogged refrigerant circuit; 7 LEV malfunction. Heating: 1 Reduced water flow; 2 Low temperature; 3 Defective water pump; 4 Leakage or shortage of refrigerant; 5 LEV malfunction.

On the Ecodan Zubadan Puhz Hw Monobloc

The manual says: Freezing/overheating protection is working (plate heat exchanger freeze protection detected by outdoor unit).

Part involved: Plate heat exchanger / water flow / refrigerant charge.

When it shows: Cooling: plate HEX pipe TH6 <= -5C for 10 s, or <= -2C at minimum frequency for 5 min after 6 min running. Heating/defrost (inlet water TH32 <= 15C): TH6 <= -6C for 30 s after 1 min of defrost, or TH6 <= -16C for 10 s during defrost.

Likely causes:

  • Cooling: 1 Reduced water flow (clogged filter, leak); 2 Low temperature (low load, inlet water too cold); 3 Defective water pump; 4 Defective outdoor fan control; 5 Overcharge of refrigerant; 6 Clogged refrigerant circuit; 7 LEV malfunction. Heating: 1 Reduced water flow; 2 Low temperature; 3 Defective water pump; 4 Leakage or shortage of refrigerant; 5 LEV malfunction.

On the Ecodan Zubadan Puhz Shw Split

The manual says: Freezing/overheating protection is working - overheating protection in heating mode (split outdoor unit).

Part involved: Pressure sensor 63HS / refrigerant charge / water flow at indoor plate HEX.

When it shows: Heating: condensing temperature from 63HS >= Tcond (ambient-dependent, approx. 63C at -18C falling to 50-51C at higher ambients) with compressor frequency <= 25 Hz; not detected during defrost.

Likely causes:

  • 1 Overcharge of refrigerant; 2 Defective refrigerant circuit (clogs); 3 Malfunction of linear expansion valve; 4 Reduced water flow (clogged filter, water leak); 5 High temperature (overload, inlet water too warm); 6 Defective water pump.

Is it safe?

On the Ecodan

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-resetting; code remains until reset.

Manual reset: Installation manuals: press F4 (RESET) then F3 (Yes) on the main remote controller (older controllers: hold button E for 3 s); 'To cancel error codes please switch system off'. Fix the cause first.

On the Ecodan Hydrodan

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-resetting; code remains until reset.

Manual reset: Installation manuals: press F4 (RESET) then F3 (Yes) on the main remote controller (older controllers: hold button E for 3 s); 'To cancel error codes please switch system off'. Fix the cause first.

On the Ecodan Puhz Sw Split

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering in the service manual; code is logged in the outdoor unit error history.

Manual reset: Clear via RESET on the main remote controller after the cause is fixed; service manual actions include switching power off and on to recheck.

On the Ecodan Puhz W Monobloc

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering in the service manual; code is logged in the outdoor unit error history.

Manual reset: Clear via RESET on the main remote controller after the cause is fixed; service manual actions include switching power off and on to recheck.

On the Ecodan R290 Puz Wz

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering in the service manual; code is logged in the outdoor unit error history.

Manual reset: Clear via RESET on the main remote controller after the cause is fixed; service manual actions include switching power off and on to recheck.

On the Ecodan R32 Puz Wm

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering in the service manual; code is logged in the outdoor unit error history.

Manual reset: Clear via RESET on the main remote controller after the cause is fixed; service manual actions include switching power off and on to recheck.

On the Ecodan R32 Zubadan Puz Hwm

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering in the service manual; code is logged in the outdoor unit error history.

Manual reset: Clear via RESET on the main remote controller after the cause is fixed; service manual actions include switching power off and on to recheck.

On the Ecodan Ultra Quiet Puhz W Vaa

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering in the service manual; code is logged in the outdoor unit error history.

Manual reset: Clear via RESET on the main remote controller after the cause is fixed; service manual actions include switching power off and on to recheck.

On the Ecodan Zubadan Puhz Hw Monobloc

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering in the service manual; code is logged in the outdoor unit error history.

Manual reset: Clear via RESET on the main remote controller after the cause is fixed; service manual actions include switching power off and on to recheck.

On the Ecodan Zubadan Puhz Shw Split

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering in the service manual; code is logged in the outdoor unit error history.

Manual reset: Clear via RESET on the main remote controller after the cause is fixed; service manual actions include switching power off and on to recheck.

What you can check

  • Note the code, unit and ref. address shown on the main remote controller and contact your installer (Mitsubishi user manuals: 'Make a note of the error code number and contact installer'). Check the heat pump breaker/isolator at the consumer unit is on and read the primary system pressure gauge (if fitted) so you can report it. A single reset from the main remote controller (RESET, then Yes) may be tried; if the code returns, do not keep resetting. Do not open the outdoor unit, cylinder/hydrobox or any casing. Check the primary circuit pressure gauge (typically about 1-2 bar when cold on sealed systems) and look for visible leaks; do not top up or bleed unless your installer has shown you how and the filling loop is then closed.

What the engineer will check

On the Ecodan

  • Check water flow, strainer, pump; check refrigerant charge.
  • 1-2 Check water piping, filter, leaks; 3 Check water pump; 4 Check outdoor fan motor; 5-6 Check refrigerant circuit operating condition, correct refrigerant amount; 7 Check LEV; 8 Check pressure sensor / DIP SW5-3 to 5-7 capacity code. Install manuals: 'See Action for L3. Check for correct amount of refrigerant.'.

Who to ask for: Heat pump installer / heating engineer (hydraulic circuit); Mitsubishi Ecodan-trained engineer for FTC diagnostics.

On the Ecodan Hydrodan

  • 1-2 Check water piping, filter, leaks; 3 Check water pump; 4 Check outdoor fan motor; 5-6 Check refrigerant circuit operating condition, correct refrigerant amount; 7 Check LEV; 8 Check pressure sensor / DIP SW5-3 to 5-7 capacity code. Install manuals: 'See Action for L3. Check for correct amount of refrigerant.'.

Who to ask for: Heat pump installer / heating engineer (hydraulic circuit); Mitsubishi Ecodan-trained engineer for FTC diagnostics.

On the Ecodan Puhz Sw Split

  • 1-2 Check operating condition of refrigerant circuit; 3 Check linear expansion valve; 4-5 Check water piping; 6 Check water pump.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (refrigeration / F-gas).

Certification: UK F-gas Category I certification (R410A).

On the Ecodan Puhz W Monobloc

  • 1-2 Check water piping (filter/strainer, leaks, flow); 3 Check water pump; 4 Check outdoor fan motor (cooling); 5-7 Check refrigerant circuit operating condition / correct refrigerant amount; check linear expansion valve.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (refrigeration / F-gas) / heating engineer (water circuit).

Certification: UK F-gas Category I certification (R410A) (if refrigerant circuit work is needed).

On the Ecodan R290 Puz Wz

  • 1-2 Check water piping (filter/strainer, leaks, flow); 3 Check water pump; 4 Check outdoor fan motor (cooling); 5-7 Check refrigerant circuit operating condition / correct refrigerant amount; check linear expansion valve.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (refrigeration / F-gas) / heating engineer (water circuit).

Certification: UK F-gas Category I certification plus competence for flammable A3 refrigerant (R290) (if refrigerant circuit work is needed).

On the Ecodan R32 Puz Wm

  • 1-2 Check water piping (filter/strainer, leaks, flow); 3 Check water pump; 4 Check outdoor fan motor (cooling); 5-7 Check refrigerant circuit operating condition / correct refrigerant amount; check linear expansion valve.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (refrigeration / F-gas) / heating engineer (water circuit).

Certification: UK F-gas Category I certification (R32, A2L mildly flammable) (if refrigerant circuit work is needed).

On the Ecodan R32 Zubadan Puz Hwm

  • 1-2 Check water piping (filter/strainer, leaks, flow); 3 Check water pump; 4 Check outdoor fan motor (cooling); 5-7 Check refrigerant circuit operating condition / correct refrigerant amount; check linear expansion valve.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (refrigeration / F-gas) / heating engineer (water circuit).

Certification: UK F-gas Category I certification (R32, A2L mildly flammable) (if refrigerant circuit work is needed).

On the Ecodan Ultra Quiet Puhz W Vaa

  • 1-2 Check water piping (filter/strainer, leaks, flow); 3 Check water pump; 4 Check outdoor fan motor (cooling); 5-7 Check refrigerant circuit operating condition / correct refrigerant amount; check linear expansion valve.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (refrigeration / F-gas) / heating engineer (water circuit).

Certification: UK F-gas Category I certification (R410A) (if refrigerant circuit work is needed).

On the Ecodan Zubadan Puhz Hw Monobloc

  • 1-2 Check water piping (filter/strainer, leaks, flow); 3 Check water pump; 4 Check outdoor fan motor (cooling); 5-7 Check refrigerant circuit operating condition / correct refrigerant amount; check linear expansion valve.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (refrigeration / F-gas) / heating engineer (water circuit).

Certification: UK F-gas Category I certification (R410A) (if refrigerant circuit work is needed).

On the Ecodan Zubadan Puhz Shw Split

  • 1-2 Check operating condition of refrigerant circuit; 3 Check linear expansion valve; 4-5 Check water piping; 6 Check water pump.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (refrigeration / F-gas).

Certification: UK F-gas Category I certification (R410A).

What you might notice

What owners and engineers report

27 owner and engineer reports mention this.

  • No heating on the Ecodan: 9 reports
  • No hot water on the Ecodan: 9 reports
  • Frequent defrosting on the Ecodan: 3 reports
  • Pressure keeps dropping on the Ecodan: 2 reports
  • Frequent defrosting on the Ecodan Puhz W Monobloc: 1 report
  • Pressure keeps dropping on the Ecodan Puhz W Monobloc: 1 report
  • Frequent defrosting on the Ecodan R32 Puz Wm: 1 report
  • Pressure keeps dropping on the Ecodan R32 Puz Wm: 1 report

Sources

A code explains what the controller detected, not a confirmed root cause.