SolarpunkHomes
Sign inCall us · +44 7510 081687
Heat pumps
Heat pumps · Error codes · Mitsubishi Electric
LFMitsubishi Electric

LF on a Mitsubishi Electric heat pump: Flow sensor failure

Short answer

On a Mitsubishi Electric heat pump, LF means: Flow sensor failure. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 2 sources

What it means

On the Ecodan

The manual says: Flow sensor failure.

Part involved: Primary circuit flow sensor.

When it shows: Flow sensor signal lost (disconnection or loose connection).

Likely causes:

  • Disconnection or loose connection of flow sensor.

On the Ecodan Co2 Quhz

The manual says: Flow sensor failure (flow sensors 1, A, B).

Part involved: Flow sensors 1, A, B.

When it shows: Flow sensor signal abnormal (request code 575 identifies sensor).

Likely causes:

  • Flow sensor cable damage or loose connection.

Is it safe?

On the Ecodan

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-resetting; code remains until reset.

Manual reset: Installation manuals: press F4 (RESET) then F3 (Yes) on the main remote controller (older controllers: hold button E for 3 s); 'To cancel error codes please switch system off'. Fix the cause first.

On the Ecodan Co2 Quhz

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering.

Manual reset: Press F4 (Reset) then F3 (Yes) on the main remote controller, or switch system off (installation manual).

What you can check

  • Note the code, unit and ref. address shown on the main remote controller and contact your installer (Mitsubishi user manuals: 'Make a note of the error code number and contact installer'). Check the heat pump breaker/isolator at the consumer unit is on and read the primary system pressure gauge (if fitted) so you can report it. A single reset from the main remote controller (RESET, then Yes) may be tried; if the code returns, do not keep resetting. Do not open the outdoor unit, cylinder/hydrobox or any casing.

What the engineer will check

On the Ecodan

  • Check flow sensor cable for damage or loose connections; replace sensor if faulty.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (controls / wiring).

On the Ecodan Co2 Quhz

  • Check flow sensor cable for damage or loose connections.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (controls / wiring).

What you might notice

What owners and engineers report

18 owner and engineer reports mention this.

  • No heating on the Ecodan: 9 reports
  • No hot water on the Ecodan: 9 reports

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026