LC on a Mitsubishi Electric Ecodan: Boiler circulation water temperature overheat protection (hybrid/boiler systems)

Short answer

On a Mitsubishi Electric heat pump, LC means: Boiler circulation water temperature overheat protection (hybrid/boiler systems). The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Boiler circulation water temperature overheat protection (hybrid/boiler systems).

Part involved: Boiler flow thermistors THWB1/THWB2; boiler circuit.

When it shows: THWB1 (or THWB2) >= 80C for 10 consecutive seconds.

Likely causes:

  • 1 Boiler set temperature too high; 2 Reduced flow in boiler heating circuit (water leakage, strainer blockage, pump function).

Is it safe?

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-resetting; code remains until reset.

Manual reset: Installation manuals: press F4 (RESET) then F3 (Yes) on the main remote controller (older controllers: hold button E for 3 s); 'To cancel error codes please switch system off'. Fix the cause first.

What you can check

  • Note the code, unit and ref. address shown on the main remote controller and contact your installer (Mitsubishi user manuals: 'Make a note of the error code number and contact installer'). Check the heat pump breaker/isolator at the consumer unit is on and read the primary system pressure gauge (if fitted) so you can report it. A single reset from the main remote controller (RESET, then Yes) may be tried; if the code returns, do not keep resetting. Do not open the outdoor unit, cylinder/hydrobox or any casing. Check the primary circuit pressure gauge (typically about 1-2 bar when cold on sealed systems) and look for visible leaks; do not top up or bleed unless your installer has shown you how and the filling loop is then closed.

What the engineer will check

  • 1 Check boiler set temperature against restriction (thermistor kit PAC-TH011HT-E / PAC-TH012HT(L)-E manual); 2 Check for leaks, strainer blockage and pump function.

Who to ask for: Heat pump installer / heating engineer (hydraulic circuit); Mitsubishi Ecodan-trained engineer for FTC diagnostics.

What you might notice

What owners and engineers report

9 owner and engineer reports mention this.

  • No heating on the Ecodan: 9 reports

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026