LED-9B on an Ideal Heating Logic Air: Circulation pump error

Short answer

On an Ideal Heating heat pump, LED-9B means: Circulation pump error. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Circulation pump error.

Part involved: outdoor unit circulation pump.

When it shows: 2 s after pump power-on, pump feedback out of range; compressor and pump stop.

Likely causes:

  • 1. Sludge filter trap clogged 2. Circulating pump blocked/failed/malfunctioning 3. Pump-PCB connection.

Is it safe?

Does the heat pump stop?Yes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

What you can check

  • Note the code or fault message shown on the controller/Halo and when it appeared; check the heat pump's isolator and consumer-unit breaker are on. Read the heating system pressure gauge (compare it with the pressure your installer set) and report it; check the filling loop is closed.

What the engineer will check

  • Read pump fault status on indoor HMI; check pump not blocked and correctly supplied; replace circulation pump; if persists replace hydraulic PCB and main PCB.

Who to ask for: Heat pump engineer; casing removal only by persons competent with R32 (A2L); refrigerant-circuit work requires Cat I/II F-gas certification (I&M p.75 warning).

Certification: F-gas Cat I/II for refrigerant work; electrical work by competent person.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026