LED-97 on an Ideal Heating Logic Air: Outdoor unit fan motor 1 error

Short answer

On an Ideal Heating heat pump, LED-97 means: Outdoor unit fan motor 1 error. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Outdoor unit fan motor 1 error.

Part involved: outdoor fan motor.

When it shows: Fan <100 rpm 20 s after start; after 3 repeats within 60 s compressor and fan stop; 5 repeats -> permanent stop.

Likely causes:

  • 1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Inverter PCB failure 4. Main PCB failure 5. Fan motor failure.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

What you can check

  • Note the code or fault message shown on the controller/Halo and when it appeared; check the heat pump's isolator and consumer-unit breaker are on. Check the outdoor unit is not blocked by snow, ice, leaves or stored items and that air can flow freely around it.

What the engineer will check

  • Rotate fan by hand (power off) for seizure/obstruction; check ambient around motor; check fan motor (Parts Information 4); check inverter PCB output (P650: Red-Black 280-373 V DC, White-Black 15 +/-1.5 V); replace fan motor/main PCB.

Who to ask for: Heat pump engineer; casing removal only by persons competent with R32 (A2L); refrigerant-circuit work requires Cat I/II F-gas certification (I&M p.75 warning).

Certification: F-gas Cat I/II for refrigerant work; electrical work by competent person.

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026