LED-86-pressure-sensor on an Ideal Heating Logic Air: Pressure sensor error

Short answer

On an Ideal Heating heat pump, LED-86-pressure-sensor means: Pressure sensor error. The manual does not say whether the heat pump stops. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Pressure sensor error.

Part involved: high pressure sensor (P20).

When it shows: 30 s after power-on, sensor value Ps <=0 or >=5 MPa for 30 s continuously.

Likely causes:

  • 1. Connector connection failure 2. Pressure sensor failure 3. Main PCB failure.

Is it safe?

Does the heat pump stop?Not stated
Engineer needed?Yes

The manual does not say whether the heat pump stops.

What you can check

  • Note the code or fault message shown on the controller/Halo and when it appeared; check the heat pump's isolator and consumer-unit breaker are on.

What the engineer will check

  • Check sensor connector; check main PCB supply 5 V +/-5% (pin 1-3); check sensor output (pin 2-3, 0.5-4.5 V over 0-5 MPa); replace sensor or main PCB.

Who to ask for: Heat pump engineer; casing removal only by persons competent with R32 (A2L); refrigerant-circuit work requires Cat I/II F-gas certification (I&M p.75 warning).

Certification: F-gas Cat I/II for refrigerant work; electrical work by competent person.

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026