LED-84 on an Ideal Heating Logic Air: Current sensor error
Short answer
On an Ideal Heating heat pump, LED-84 means: Current sensor error. The manual does not say whether the heat pump stops. An engineer is needed to fix the cause.
Reviewed 23 September 2026 · 1 source
What it means
The manual says: Current sensor error.
Part involved: outdoor inverter PCB input current sensor.
When it shows: Input current sensor detects 1 A or less while compressor runs >50 rps, 1 min after start (except defrost).
Likely causes:
- 1. Defective connection of electrical components 2. External cause 3. Inverter PCB failure.
Is it safe?
| Does the heat pump stop? | Not stated |
|---|---|
| Engineer needed? | Yes |
The manual does not say whether the heat pump stops.
What you can check
- Note the code or fault message shown on the controller/Halo and when it appeared; check the heat pump's isolator and consumer-unit breaker are on. If the fault clears after the installer-approved restart via the controller and does not return, note it for the next service; if it returns, call an engineer. Check whether lights or other appliances are also affected (possible supply problem) and whether any breaker/RCD has tripped - do not reset repeatedly.
What the engineer will check
- Power cycle; check external causes (voltage drop, noise, earthing); check connectors/terminals/cables; replace inverter PCB.
Who to ask for: Heat pump engineer; casing removal only by persons competent with R32 (A2L); refrigerant-circuit work requires Cat I/II F-gas certification (I&M p.75 warning).
Certification: F-gas Cat I/II for refrigerant work; electrical work by competent person.
Sources
- Maintenance Manual LOGIC AIR 8-10 Air/water heat pump Monobloc system (U0753484_2451_EN_1) ↗ · U0753484_2451_EN_1 · page 23 · Reviewed 23 September 2026
A code explains what the controller detected, not a confirmed root cause.
Reviewed: 23 September 2026