LED-77Ideal Heating · Logic Air

LED-77 on an Ideal Heating Logic Air: Heat sink temp. sensor error

Short answer

On an Ideal Heating heat pump, LED-77 means: Heat sink temp. sensor error. The manual does not say whether the heat pump stops. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Heat sink temp. sensor error.

Part involved: inverter heatsink thermistor.

When it shows: Thermistor short or open detected.

Likely causes:

  • 1. Connector connection failure/open 2. Thermistor failure 3. PCB failure (inverter PCB).

Is it safe?

Does the heat pump stop?Not stated
Engineer needed?Yes

The manual does not say whether the heat pump stops.

What you can check

  • Note the code or fault message shown on the controller/Halo and when it appeared; check the heat pump's isolator and consumer-unit breaker are on.

What the engineer will check

  • Check connector and cable continuity; disconnect thermistor and check characteristic (Service Parts Information 5); check PCB reference voltage Inverter PCB P700:1-3 = 5 V; replace thermistor or PCB.

Who to ask for: Heat pump engineer; casing removal only by persons competent with R32 (A2L); refrigerant-circuit work requires Cat I/II F-gas certification (I&M p.75 warning).

Certification: F-gas Cat I/II for refrigerant work; electrical work by competent person.

Sources

A code explains what the controller detected, not a confirmed root cause.