COMPRESSOR-ERROR on a Heliotherm Basic Comfort air split: High/low pressure difference falls below 3.5 bar

Short answer

On a Heliotherm heat pump, COMPRESSOR-ERROR means: High/low pressure difference falls below 3.5 bar. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: High/low pressure difference falls below 3.5 bar.

Part involved: Compressor error.

Likely causes:

  • U_Block not connected - compressor not running.
  • Wrong compressor rotation direction.
  • No power supply to compressor.
  • 4-way valve in middle position.
  • Energy source to heating water temperature difference too low.

Is it safe?

Switch the heat pump off at its isolator and call an engineer.

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Manual reset: Fault clearance function in the controller main menu (web control 321 manual p.27, intended for the Heliotherm competence partner).

What you can check

  • Note the error text shown on the controller and contact your Heliotherm competence partner.
  • Check the heating system pressure gauge reading.

What the engineer will check

  • Connect U_Block contact.
  • Correct rotation direction.
  • Check fuses and cables.
  • Increase compressor start speed.
  • Restrict heating-side mass flow.

Who to ask for: heat pump / refrigeration (Heliotherm competence partner).

Certification: F-gas certification for refrigerant work.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026