F.734 on a Glow-worm GeniaAir: Condensation temperature too low

Short answer

On a Glow-worm heat pump, F.734 means: Condensation temperature too low. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Condensation temperature too low.

Part involved: Condensation temperature too low.

Likely causes:

  • The temperature in the building circuit is too low; outside of the operating characteristics. Refrigerant volume too low.
  • Glow-worm trade page: Condensation temperature too low Electronic expansion valve fault, fault in the electrical connection of the compressor inlet temperature sensor, compressor inlet temperature sensor fault, low refrigerant volume, fault in the electrical connection of the high pressure sensor, high pressure sensor fault, building circuit pressure too ….

Is it safe?

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: no - the fault remains displayed until the cause is eliminated.

Manual reset: yes - after the cause is eliminated, press the reset button (indoor unit) or reset via the system control; if it recurs after several resets contact customer service.

What you can check

  • Note the full code and text shown on the display (and the date/time it appeared). Check the outdoor unit's air inlet and outlet are not blocked by leaves, debris, snow or ice build-up and clear any loose debris from around it (do not open the casing, poke the fins or use tools). Glow-worm's MiPro Sense operating instructions say always contact your competent person in the event of a fault message; until they arrive you may select a limp-home (back-up heater) setting on the control, which is expensive to run. If you smell gas/solvent near the outdoor unit or hear hissing, switch the heat pump off at the isolator, keep ignition sources away and call an engineer.

What the engineer will check

  • Check the EEV (does the EEV move to the limit stop? Use the sensor/actuator test). 2. Check the compressor inlet sensor. 3. Check the refrigerant filling volume (see technical data). 4. Check the high-pressure sensor. 5. Check the pressure sensor in the building circuit.

Who to ask for: F-gas certified refrigeration engineer with heat pump experience (R290 flammable-refrigerant competence required for aroTHERM plus / GeniaAir).

Certification: F-gas Category I (Regulation (EU) 517/2014 as retained in GB) certificate; flammable (R290) refrigerant training for R290 units.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026