Heat pumps · Error codes · Carrier
3Carrier

3 on a Carrier heat pump: Frozen plates exchanger (plate heat exchanger froze during cooling); restart only by power OFF-ON after qualified check

Short answer

On a Carrier heat pump, 3 means: Frozen plates exchanger (plate heat exchanger froze during cooling); restart only by power OFF-ON after qualified check. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 2 sources

What it means

On the AquaSnap / AquaSnap Plus 30AWH (R410A inverter monobloc, 2010-2018 generations)

The manual says: Frozen plates exchanger (plate heat exchanger froze during cooling); restart only by power OFF-ON after qualified check.

Likely causes:

  • Low water flow/volume or low set-point in cooling.

On the AquaSnap Plus 30AWH (R410A monobloc)

The manual says: Enter water Temperature Sensor (EWT).

Likely causes:

  • Check the entering water temperature sensor (EWT).
  • check the GMC board.

Is it safe?

On the AquaSnap / AquaSnap Plus 30AWH (R410A inverter monobloc, 2010-2018 generations)

Switch the heat pump off at its isolator and call an engineer.

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Code 3 (frozen plate exchanger): only restart is power OFF-ON after qualified service check (manual p26).

On the AquaSnap Plus 30AWH (R410A monobloc)

Does the heat pump stop?Yes
SeverityFault — clears by itself when the condition goes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

What you can check

On the AquaSnap / AquaSnap Plus 30AWH (R410A inverter monobloc, 2010-2018 generations)

  • Note the code/LED pattern and the model from the rating plate, then contact a heat pump/refrigeration engineer.
  • Check the heat pump's breaker/isolator at the consumer unit is on.
  • Check the heating system pressure gauge reads in the normal range stated by the installer (usually about 1-1.5 bar cold) and that the filling loop is closed.

On the AquaSnap Plus 30AWH (R410A monobloc)

  • Read and note the exact code shown on the controller display.
  • Check the heat pump's breaker/isolator at the consumer unit is on.
  • Restart once via the controller (OFF then ON) as the manual allows; if the code returns, call an engineer.

What the engineer will check

On the AquaSnap / AquaSnap Plus 30AWH (R410A inverter monobloc, 2010-2018 generations)

  • Check pump, flow switch, strainer, valves, water volume and antifreeze setting.

Who to ask for: refrigeration / heat pump engineer.

Certification: Electrical competence for work inside the unit.

On the AquaSnap Plus 30AWH (R410A monobloc)

  • Check the entering water temperature sensor (EWT).
  • check the GMC board.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026