E171 on a Trianco heat pump: Syst1: Antifreezing Prot

Short answer

On a Trianco heat pump, E171 means: Syst1: Antifreezing Prot. The manual does not say whether the heat pump stops. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 4 sources

What it means

On the Activair Commercial R290 50kW (FG9550)

The manual says: Syst1: Antifreezing Prot.

Part involved: ambient / water temperature protection logic.

Likely causes:

  • The water flow of the system is insufficient.

On the Activair High Temperature R290 (5/9/15/22kW)

The manual says: Anti-freezing Protection.

Part involved: ambient / water temperature protection logic.

Likely causes:

  • Inlet water <= A04C and antifreeze temp <= A04-A05C.

On the Activair R290 Indoor (3.2kW wall hung / 5kW floor standing)

The manual says: Anti-freezing Fault.

Part involved: ambient / water temperature protection logic.

Likely causes:

  • Use side water system temp. is low.

On the Activair Pro (AI) R290 6/12/17kW

The manual says: Anti-freezing Fault.

Part involved: ambient / water temperature protection logic.

Likely causes:

  • Use side water system temp. is low.

Is it safe?

Does the heat pump stop?Not stated
Engineer needed?Yes

The manual does not say whether the heat pump stops.

What you can check

  • Note the exact code shown on the controller (a photo helps) and report it to your installer or the manufacturer's service line.
  • Check the heat pump's supply breaker/isolator at the consumer unit is on (do not open any casing).
  • Check the outdoor unit is not blocked by snow, ice build-up or debris.
  • Leave the heat pump powered: frost protection needs a permanent electricity supply.

What the engineer will check

On the Activair Commercial R290 50kW (FG9550)

  • Inspect whether the water flow of the water pipe conforms to related requirements and check the water pump for any blockage.

Who to ask for: heating / hydraulics.

Certification: Competent heating engineer.

On the Activair High Temperature R290 (5/9/15/22kW)

  • Check the water flow.
  • Check the outlet water temp sensor.
  • Measure the ambient temp.
  • Detect the connection of cables.
  • Check the defrost record (defrost too long or too often).

Who to ask for: heating / hydraulics.

Certification: Competent heating engineer.

On the Activair R290 Indoor (3.2kW wall hung / 5kW floor standing)

  • Check the water temp. or change the temp. sensor.
  • Check the pipe water flow and whether water system is jammed or not.

Who to ask for: heating / hydraulics.

Certification: Competent heating engineer.

On the Activair Pro (AI) R290 6/12/17kW

  • Check the water temp. or change the temp. sensor.
  • Check the pipe water flow and whether water system is jammed or not.

Who to ask for: heating / hydraulics.

Certification: Competent heating engineer.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.