LOW-PRESSURE on a Stiebel Eltron WPM 3 heat pump manager: The low pressure sensor/minimum low pressure limiter has responded (switching point depends on HP type, e.g. 1.2 bar abs within 60 s for type 1; <2 bar for 10 s type 3; <1.0 bar for 240 s type 4)

Short answer

On a Stiebel Eltron heat pump, LOW-PRESSURE means: The low pressure sensor/minimum low pressure limiter has responded (switching point depends on HP type, e.g. 1.2 bar abs within 60 s for type 1; <2 bar for 10 s type 3; <1.0 bar for 240 s type 4). The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: The low pressure sensor/minimum low pressure limiter has responded (switching point depends on HP type, e.g. 1.2 bar abs within 60 s for type 1; <2 bar for 10 s type 3; <1.0 bar for 240 s type 4).

Part involved: compressor / expansion valve / pressure switches.

When it shows: The low pressure sensor/minimum low pressure limiter has responded (switching point depends on HP type, e.g. 1.2 bar abs within 60 s for type 1; <2 bar for 10 s type 3; <1.0 bar for 240 s type 4).

Likely causes:

  • Refrigerant leak/escaped; expansion valve does not open; (type 4) check fan and fuse.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — clears by itself when the condition goes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: yes - restarts after IWS fault time/idle time.

Manual reset: after 5 faults in 2 h run: IWS reset.

What you can check

  • Read and note the full message code and time from the WPM display (DIAGNOSIS / NOTIFICATIONLIST if accessible without a code).
  • Check the heat pump and controller circuit breakers/isolators at the consumer unit are on.
  • Check the outdoor unit air intake/discharge is not blocked by leaves, snow or ice (air source units).

What the engineer will check

  • Refrigerant leak/escaped; expansion valve does not open; (type 4) check fan and fuse.

Who to ask for: F-gas/refrigeration-qualified heat pump engineer (R290/A3 flammable-refrigerant competence for R290 models).

Certification: F-gas certification for fluorinated refrigerants (R410A/R454C); flammable refrigerant (R290) handling training for R290 models.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.