Heat pumps · Error codes · Mitsubishi Heavy Industries Air-Conditioning Europe
228Mitsubishi Heavy Industries Air-Conditioning Europe · Hydrolution (split, FDCW outdoor units)

228 on a Mitsubishi Heavy Industries Air-Conditioning Europe Hydrolution: Failed defrosting: Failed 10 consecutive defrostings

Short answer

On a Mitsubishi Heavy Industries Air-Conditioning Europe heat pump, 228 means: Failed defrosting: Failed 10 consecutive defrostings. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Failed defrosting: Failed 10 consecutive defrostings.

Part involved: Failed defrosting.

When it shows: Failed 10 consecutive defrostings.

Likely causes:

  • System temperature too low and/or poor flow; insufficient available system volume; significant wind effect; clogged particle filter.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: no.

Manual reset: yes (select 'reset alarm' in the alarm menu).

What you can check

  • Note the alarm number/text shown on the display. Check the consumer-unit breakers/isolators for the indoor and outdoor units are on. Check the outdoor unit is not blocked by leaves, snow or ice and its drain is clear (look only - do not open the casing). Check radiator/underfloor thermostats in the house are not all closed (user manual). Check the heating system pressure gauge reads in the normal range (about 0.5-1.5 bar when cold for Hydrolution per user manual). On the RC-HY controller you may select 'reset alarm' once (installation manual: 'in most cases it is enough'); if the red lamp stays or the alarm returns, select 'aid mode' (if enabled) or 'add. heat only' in menu 4.2 and contact the installer.

What the engineer will check

  • Per manual 'May be due to': System temperature too low and/or poor flow; insufficient available system volume; significant wind effect; clogged particle filter. Check sensor wiring/resistance, settings, flow (particle filter, pump) and supply as applicable.

Who to ask for: Heat pump / refrigeration engineer (manufacturer-trained).

Certification: F-gas certification for refrigerant-circuit work; electrical competence (Part P/18th Edition) for PCB/wiring.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026