Heat pumps · Error codes · Mitsubishi Electric
ECMitsubishi Electric

EC on a Mitsubishi Electric heat pump: Start time exceeded: outdoor microcomputer cannot receive communication

Short answer

On a Mitsubishi Electric heat pump, EC means: Start time exceeded: outdoor microcomputer cannot receive communication. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 9 sources

What it means

On the Ecodan Co2 Quhz

The manual says: Start time exceeded: outdoor microcomputer cannot receive communication.

Part involved: Cylinder unit-outdoor power/transmission line.

When it shows: Inability to receive communication detected on outdoor unit microcomputer.

Likely causes:

  • 1 Defective power transmission line connection; 2 Defective outdoor inverter PCB; 3 Defective cylinder unit control board; 4 Noise.

On the Ecodan Puhz Sw Split

The manual says: Startup time over: the unit cannot finish its startup process within 4 minutes after power on.

Part involved: Indoor (FTC)/outdoor connecting wire.

When it shows: Startup process not finished within 4 minutes of power-on.

Likely causes:

  • 1 Contact failure of indoor/outdoor connecting wire; 2 Wire diameter or length out of specification; 3 Refrigerant address 0 used on slave unit (multiple outdoor units control); 4 Noise on power supply or connecting wire.

On the Ecodan Puhz W Monobloc

The manual says: Startup time over: the unit cannot finish its startup process within 4 minutes after power on.

Part involved: Indoor (FTC)/outdoor connecting wire.

When it shows: Startup process not finished within 4 minutes of power-on.

Likely causes:

  • 1 Contact failure of indoor/outdoor connecting wire; 2 Wire diameter or length out of specification; 3 Refrigerant address 0 used on slave unit (multiple outdoor units control); 4 Noise on power supply or connecting wire.

On the Ecodan R290 Puz Wz

The manual says: Startup time over: the unit cannot finish its startup process within 4 minutes after power on.

Part involved: Indoor (FTC)/outdoor connecting wire.

When it shows: Startup process not finished within 4 minutes of power-on.

Likely causes:

  • 1 Contact failure of indoor/outdoor connecting wire; 2 Wire diameter or length out of specification; 3 Refrigerant address 0 used on slave unit (multiple outdoor units control); 4 Noise on power supply or connecting wire.

On the Ecodan R32 Puz Wm

The manual says: Startup time over: the unit cannot finish its startup process within 4 minutes after power on.

Part involved: Indoor (FTC)/outdoor connecting wire.

When it shows: Startup process not finished within 4 minutes of power-on.

Likely causes:

  • 1 Contact failure of indoor/outdoor connecting wire; 2 Wire diameter or length out of specification; 3 Refrigerant address 0 used on slave unit (multiple outdoor units control); 4 Noise on power supply or connecting wire.

On the Ecodan R32 Zubadan Puz Hwm

The manual says: Startup time over: the unit cannot finish its startup process within 4 minutes after power on.

Part involved: Indoor (FTC)/outdoor connecting wire.

When it shows: Startup process not finished within 4 minutes of power-on.

Likely causes:

  • 1 Contact failure of indoor/outdoor connecting wire; 2 Wire diameter or length out of specification; 3 Refrigerant address 0 used on slave unit (multiple outdoor units control); 4 Noise on power supply or connecting wire.

On the Ecodan Ultra Quiet Puhz W Vaa

The manual says: Startup time over: the unit cannot finish its startup process within 4 minutes after power on.

Part involved: Indoor (FTC)/outdoor connecting wire.

When it shows: Startup process not finished within 4 minutes of power-on.

Likely causes:

  • 1 Contact failure of indoor/outdoor connecting wire; 2 Wire diameter or length out of specification; 3 Refrigerant address 0 used on slave unit (multiple outdoor units control); 4 Noise on power supply or connecting wire.

On the Ecodan Zubadan Puhz Hw Monobloc

The manual says: Startup time over: the unit cannot finish its startup process within 4 minutes after power on.

Part involved: Indoor (FTC)/outdoor connecting wire.

When it shows: Startup process not finished within 4 minutes of power-on.

Likely causes:

  • 1 Contact failure of indoor/outdoor connecting wire; 2 Wire diameter or length out of specification; 3 Refrigerant address 0 used on slave unit (multiple outdoor units control); 4 Noise on power supply or connecting wire.

On the Ecodan Zubadan Puhz Shw Split

The manual says: Startup time over: the unit cannot finish its startup process within 4 minutes after power on.

Part involved: Indoor (FTC)/outdoor connecting wire.

When it shows: Startup process not finished within 4 minutes of power-on.

Likely causes:

  • 1 Contact failure of indoor/outdoor connecting wire; 2 Wire diameter or length out of specification; 3 Refrigerant address 0 used on slave unit (multiple outdoor units control); 4 Noise on power supply or connecting wire.

Is it safe?

On the Ecodan Co2 Quhz

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering.

Manual reset: Outdoor error cancelled by switching the cylinder unit earth leakage circuit breaker OFF, waiting until the outdoor board LEDs go out (about 1 minute), then ON again (service manual GHH15010).

On the Ecodan Puhz Sw Split

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering in the service manual; code is logged in the outdoor unit error history.

Manual reset: Clear via RESET on the main remote controller after the cause is fixed; service manual actions include switching power off and on to recheck.

On the Ecodan Puhz W Monobloc

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering in the service manual; code is logged in the outdoor unit error history.

Manual reset: Clear via RESET on the main remote controller after the cause is fixed; service manual actions include switching power off and on to recheck.

On the Ecodan R290 Puz Wz

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering in the service manual; code is logged in the outdoor unit error history.

Manual reset: Clear via RESET on the main remote controller after the cause is fixed; service manual actions include switching power off and on to recheck.

On the Ecodan R32 Puz Wm

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering in the service manual; code is logged in the outdoor unit error history.

Manual reset: Clear via RESET on the main remote controller after the cause is fixed; service manual actions include switching power off and on to recheck.

On the Ecodan R32 Zubadan Puz Hwm

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering in the service manual; code is logged in the outdoor unit error history.

Manual reset: Clear via RESET on the main remote controller after the cause is fixed; service manual actions include switching power off and on to recheck.

On the Ecodan Ultra Quiet Puhz W Vaa

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering in the service manual; code is logged in the outdoor unit error history.

Manual reset: Clear via RESET on the main remote controller after the cause is fixed; service manual actions include switching power off and on to recheck.

On the Ecodan Zubadan Puhz Hw Monobloc

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering in the service manual; code is logged in the outdoor unit error history.

Manual reset: Clear via RESET on the main remote controller after the cause is fixed; service manual actions include switching power off and on to recheck.

On the Ecodan Zubadan Puhz Shw Split

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated as auto-recovering in the service manual; code is logged in the outdoor unit error history.

Manual reset: Clear via RESET on the main remote controller after the cause is fixed; service manual actions include switching power off and on to recheck.

What you can check

  • Note the code, unit and ref. address shown on the main remote controller and contact your installer (Mitsubishi user manuals: 'Make a note of the error code number and contact installer'). Check the heat pump breaker/isolator at the consumer unit is on and read the primary system pressure gauge (if fitted) so you can report it. A single reset from the main remote controller (RESET, then Yes) may be tried; if the code returns, do not keep resetting. Do not open the outdoor unit, cylinder/hydrobox or any casing. A power cycle is a Mitsubishi first step for communication codes: switching the heat pump off and on at its isolator (outdoor and indoor supplies) once is acceptable.

What the engineer will check

On the Ecodan Co2 Quhz

  • 1 Correct power transmission line connection; 2 Replace outdoor inverter PCB; 3 Replace cylinder unit control board; 4 Move power signal line away from noise source.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (controls / wiring).

On the Ecodan Puhz Sw Split

  • As EA: check connecting wire, wire size/length, refrigerant address settings, noise; power off/on and replace boards if it recurs.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (controls / wiring).

On the Ecodan Puhz W Monobloc

  • As EA: check connecting wire, wire size/length, refrigerant address settings, noise; power off/on and replace boards if it recurs.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (controls / wiring).

On the Ecodan R290 Puz Wz

  • As EA: check connecting wire, wire size/length, refrigerant address settings, noise; power off/on and replace boards if it recurs.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (controls / wiring).

On the Ecodan R32 Puz Wm

  • As EA: check connecting wire, wire size/length, refrigerant address settings, noise; power off/on and replace boards if it recurs.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (controls / wiring).

On the Ecodan R32 Zubadan Puz Hwm

  • As EA: check connecting wire, wire size/length, refrigerant address settings, noise; power off/on and replace boards if it recurs.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (controls / wiring).

On the Ecodan Ultra Quiet Puhz W Vaa

  • As EA: check connecting wire, wire size/length, refrigerant address settings, noise; power off/on and replace boards if it recurs.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (controls / wiring).

On the Ecodan Zubadan Puhz Hw Monobloc

  • As EA: check connecting wire, wire size/length, refrigerant address settings, noise; power off/on and replace boards if it recurs.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (controls / wiring).

On the Ecodan Zubadan Puhz Shw Split

  • As EA: check connecting wire, wire size/length, refrigerant address settings, noise; power off/on and replace boards if it recurs.

Who to ask for: Mitsubishi Ecodan-trained heat pump engineer (controls / wiring).

What you might notice

What owners and engineers report

1 owner and engineer report mentions this.

  • Heat pump will not start on the Ecodan Puhz W Monobloc: 1 report

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026