CH62 on a LG heat pump: Heatsink temperature high – inverter PCB heatsink/power element overheated
Short answer
On a LG heat pump, CH62 means: Heatsink temperature high – inverter PCB heatsink/power element overheated. The heat pump keeps running with some functions stopped. An engineer is needed to fix the cause.
Reviewed 23 September 2026 · 1 source
What it means
The manual says: Heatsink temperature high – inverter PCB heatsink/power element overheated.
Part involved: inverter PCB heatsink.
When it shows: Heatsink temperature over 85 °C (Hydrosplit/R290) or 110 °C (Monobloc S).
Likely causes:
- Poor IPM/PFCM screw torque, thermal grease or soldering; outdoor fan abnormal; inverter PCB defect; overload operation.
Is it safe?
| Does the heat pump stop? | Partly |
|---|---|
| Severity | Fault — clears by itself when the condition goes |
| Engineer needed? | Yes |
The heat pump keeps running with some functions stopped.
Resetting itself: yes – trouble clears when the condition is repaired; emergency operation must be restarted by the user after a power reset.
Manual reset: Not normally required; user restarts after power reset if emergency operation was running.
What you can check
- Read the code on the controller (LG shows 'CH' + number; older wired controllers alternate 'CH' and the number) and note it together with the model number. Report it to your installer or an LG-authorised service centre – LG owner's manuals say an error code generated by self-diagnosis is a reason to call the service. For this 'trouble' class LG allows temporary emergency operation: if the controller shows a pop-up offering it you may accept (OK) as a stop-gap; running costs will be higher, so do not use it long term. Emergency operation does not restart by itself after a power cut – you must switch it back on at the controller. Check (without opening any panels) that the outdoor unit is not blocked by leaves, debris, snow or ice and that nothing is stacked against the coil or fan grille.
What the engineer will check
- Isolate and wait at least 3 minutes for DC-link capacitors to discharge. Check supply voltage (1ph 230 V ±15 %, 3ph 400 V ±15 %), outdoor fan free to rotate and heat exchanger unobstructed, service valves open, EEV operation, refrigerant charge/pressures (LGMV), compressor U-V-W wiring, winding resistance and insulation resistance, IPM/IGBTM diode test, then replace inverter PCB or compressor as indicated by LGMV fault-finding.
Who to ask for: Heat pump engineer / electrician (inverter and PCB diagnostics).
Certification: Competent person for electrical work (BS 7671); isolate and wait 3 min for DC-link discharge.
What you might notice
Sources
- AIR-TO-WATER HEAT PUMP SERVICE MANUAL (General) – R32 Hydrosplit, MFL68682007 ↗ · MFL68682007 · page 72, 122 · Reviewed 23 September 2026
A code explains what the controller detected, not a confirmed root cause.
Reviewed: 23 September 2026