HbIdeal Heating · HP290

Hb on an Ideal Heating HP290: High Flow/Return Differential, 3 times in succession and Flow Temperature <7C

Short answer

On an Ideal Heating heat pump, Hb means: High Flow/Return Differential, 3 times in succession and Flow Temperature <7C. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: High Flow/Return Differential, 3 times in succession and Flow Temperature <7C.

Part involved: water circuit / plate heat exchanger freeze protection.

Likely causes:

  • Flow and return cross-connected; plate heat exchanger flow/return thermistors incorrectly installed; low water flow; 4-way valve wiring/supply fault; outdoor PCB.

Is it safe?

Does the heat pump stop?Yes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

What you can check

  • Note the code or fault message shown on the controller/Halo and when it appeared; check the heat pump's isolator and consumer-unit breaker are on. Read the heating system pressure gauge (the HP290 manual cites 1-1.5 bar) and report it; check the filling loop is closed.

What the engineer will check

  • Check flow/return orientation, thermistor installation, water flow; check 4-way valve wiring and 240 V supply; replace 4-way valve or outdoor PCB.

Who to ask for: Heat pump engineer competent with R290 (A3, highly flammable); refrigerant-circuit work requires Cat I/II F-gas plus City & Guilds 6187-21 or equivalent (I&M p.93 warning).

Certification: F-gas Cat I/II + C&G 6187-21 (R290) for refrigerant work; electrical work by competent person.

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026