LCGrant

LC on a Grant heat pump: Anti Legionella Function Not completed

Short answer

On a Grant heat pump, LC means: Anti Legionella Function Not completed. The heat pump keeps running. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 2 sources

What it means

The manual says: Anti Legionella Function Not completed.

Part involved: anti-legionella (DHW pasteurisation) cycle.

When it shows: Chofu footnote (*3): alarm resets automatically when the anti-legionella function has completed.

Likely causes:

  • DHW used during anti-legionella cycle.
  • Clogged water pump and/or water circuit.
  • Heat source setting failure.

Is it safe?

Does the heat pump stop?No
SeverityFault — clears by itself when the condition goes
Engineer needed?Yes

The heat pump keeps running.

Resetting itself: Yes (Chofu 'Auto').

Manual reset: Engineer: press - and + on the master remote controller for 3 s, or Reset SW on PCB(Terminal).

What you can check

  • Note the exact code shown on the controller display and tell your installer or Grant-trained engineer.
  • Grant advises homeowners NOT to reset Aerona3 fault codes themselves - leave the reset to the engineer.
  • Check the controller/thermostat and timer settings are as normal.

What the engineer will check

  • Check if DHW was used during anti-legionella; restart and avoid heavy DHW use during the cycle.
  • Check the pump and water circuit; clean filter.
  • Check parameters and heat source; correct settings or replace heat source.

Who to ask for: Grant-trained heat pump engineer.

What you might notice

What owners and engineers report

1 owner and engineer report mentions this.

  • Hot water not hot enough on the Aerona³ R32: 1 report

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026