E002 on an Advantix S.p.A heat pump: Low pressure alarm

Short answer

On an Advantix S.p.A heat pump, E002 means: Low pressure alarm. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 24 September 2026 · 4 sources

What it means

On the MAXA i-290 (Gamma i-290)

The manual says: Low pressure alarm.

Part involved: compressor / refrigerant circuit.

When it shows: Below 1.7 bar (cooling) / 0.7 bar (heating).

On the MAXA i-32V5

The manual says: Low pressure alarm.

Part involved: compressor / refrigerant circuit.

When it shows: Below 3.5 bar (cooling) / 1.3 bar (heating); 60 s bypass at compressor start; resets 2 bar above threshold.

On the MAXA i-32V5 MIDI (i-32V5H Midi)

The manual says: Low pressure alarm.

Part involved: compressor / refrigerant circuit.

When it shows: Below 3.5 bar (cooling) / 1.3 bar (heating); 60 s bypass at compressor start; resets 2 bar above threshold.

On the MAXA i-HPV5H

The manual says: Low pressure alarm.

Part involved: compressor / refrigerant circuit.

When it shows: Below 3.5 bar (cooling) / 1.3 bar (heating); 60 s bypass at compressor start; resets 2 bar above threshold.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — clears by itself when the condition goes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: unknown.

Manual reset: manual after 3 trips per hour.

What you can check

  • Note the code shown on the controller and the model number on the unit's rating label before contacting your installer.
  • Check that the heat pump's isolator and consumer-unit breaker are on; do not open any casing.

What the engineer will check

  • Record high/low pressures, discharge/suction temperatures and EEV steps with the unit running.
  • Check water-side flow and air-side coil (blocked/frosted fins).
  • Check pressure switches/transducers and wiring.
  • Leak-test the refrigerant circuit and correct the charge (F-gas / flammable-refrigerant competent engineer only).

Who to ask for: Heat pump engineer.

Certification: Heat pump installer competence; F-gas and flammable-refrigerant (R32/R290) handling competence for any refrigerant-circuit work.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 24 September 2026