F.715 on a Vaillant heat pump: Env. circuit: Fault contact: Pump open

Short answer

On a Vaillant heat pump, F.715 means: Env. circuit: Fault contact: Pump open. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 2 sources

What it means

On the flexoTHERM exclusive (VWF ../4)

The manual says: Env. circuit: Fault contact: Pump open.

Part involved: Fault contact: Pump open.

Likely causes:

  • The electronics system of the high-efficiency pump has detected a fault (e.g. dry running, blockage, overvoltage, undervoltage) and has switched off and locked the pump; Air in the environment circuit; Brine fluid viscosity is too high.

On the geoTHERM mini (VWS 30/4, VWS 36/4.1)

The manual says: Environment circuit: Fault contact, pump open.

Part involved: Fault contact, pump open.

Likely causes:

  • The electronics of the high-efficiency pump has detected a fault (e. g. dry running, blockage, overvoltage, undervoltage) and switched the pump off as a securing measure.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: no - the fault remains displayed until the cause is eliminated.

Manual reset: yes - after the cause is eliminated, press the reset button (indoor unit) or reset via the system control; if it recurs after several resets contact customer service.

What you can check

  • Note the full code and text shown on the display (and the date/time it appeared). Contact your installer or Vaillant Service; do not attempt any repair.

What the engineer will check

On the flexoTHERM exclusive (VWF ../4)

  • Switch the heat pump off for at least 30 seconds (no current); Check the quality of the plug contact on the PCB; Check that the pump functions correctly; Purge the environment circuit; Use a refractometer to check the mixture ratio of the brine fluid; Check the dirt filter/strainer for dirt; Check the air separator.

Who to ask for: Vaillant-trained heat pump installer/engineer (MCS-certified installer).

Certification: MCS ground-source installer; F-gas certificate for refrigerant work.

On the geoTHERM mini (VWS 30/4, VWS 36/4.1)

  • Switch the heat pump off for at least 30 seconds (no current); Check the quality of the plug contact on the PCB; Check that the pump functions correctly; Purging the environment circuit Appendix.

Who to ask for: Vaillant-trained heat pump installer/engineer (MCS-certified installer).

Certification: MCS ground-source installer; F-gas certificate for refrigerant work.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.