F.710 on a Vaillant heat pump: Env. circuit: Outlet temp. too low

Short answer

On a Vaillant heat pump, F.710 means: Env. circuit: Outlet temp. too low. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 2 sources

What it means

On the flexoTHERM exclusive (VWF ../4)

The manual says: Env. circuit: Outlet temp. too low.

Part involved: Outlet temp. too low.

Likely causes:

  • Environment circuit pump defective; Temperature sensor for environment circuit outlet defective; Volume flow too low in the environment circuit; Air in the environment circuit; Device Specific Number (DSN) setting was not applied when replacing the control PCB (HMU); Freeze protection setting was not applied when replacing the control PCB (HMU); Always check the Device Specific Number (DSN) setting.

On the geoTHERM mini (VWS 30/4, VWS 36/4.1)

The manual says: Environment circuit: Outlet temperature too low.

Part involved: Outlet temperature too low.

Likely causes:

  • Environment circuit pump defective; Temperature sensor for environment circuit outlet defective; Volume flow too low in the environment circuit; Air in the environment circuit.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: no - the fault remains displayed until the cause is eliminated.

Manual reset: yes - after the cause is eliminated, press the reset button (indoor unit) or reset via the system control; if it recurs after several resets contact customer service.

What you can check

  • Note the full code and text shown on the display (and the date/time it appeared). Contact your installer or Vaillant Service; do not attempt any repair.

What the engineer will check

On the flexoTHERM exclusive (VWF ../4)

  • Check the flow rate in the environment circuit; Check the quality of the plug contact on the PCB and on the cable harness; Check that the sensor is working correctly (resistance measurement using sensor characteristic values); Replace the sensor; Check the volume flow of the environment circuit pump (optimum spread of 3 K); Purge the environment circuit; Check the set value for the freeze protection in accordance with the environment circuit type on the control panel.

Who to ask for: Vaillant-trained heat pump installer/engineer (MCS-certified installer).

Certification: MCS ground-source installer; F-gas certificate for refrigerant work.

On the geoTHERM mini (VWS 30/4, VWS 36/4.1)

  • Check the environment circuit flow rate; Check the quality of the plug contact on the PCB and on the cable harness; Check that the sensor is working correctly (measure the resistance using the sensor characteristic values in the appendix); Replace the sensor; Check the volume flow of the environment circuit pump (optimum spread of 3 K); Purging the environment circuit.

Who to ask for: Vaillant-trained heat pump installer/engineer (MCS-certified installer).

Certification: MCS ground-source installer; F-gas certificate for refrigerant work.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.