F.1120Vaillant

F.1120 on a Vaillant heat pump: Immersion heater: Phase failure

Short answer

On a Vaillant heat pump, F.1120 means: Immersion heater: Phase failure. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 2 sources

What it means

On the aroTHERM plus (VWL ../6 A)

The manual says: Immersion heater: Phase failure.

Part involved: Phase failure.

When it shows: Internal circuit breaker trips on short circuit or failure of one (230 V) or several (400 V) current-carrying phases of the electric back-up heater.

Likely causes:

  • Internal circuit breaker has switched off because of a short circuit or failure of one (230 V) or several (400 V) current-carrying phases of the electric back-up heater; anti-legionella function not guaranteed if the heater is defective.

On the flexoTHERM exclusive (VWF ../4)

The manual says: Immersion heater: Phase failure.

Part involved: Phase failure.

Likely causes:

  • The circuit breaker in the electronics box has been triggered; Electric back-up heater defective; Poorly tightened electrical connections; Mains voltage too low; Blocked by energy supply company for over three hours.

Is it safe?

On the aroTHERM plus (VWL ../6 A)

Does the heat pump stop?Yes
SeveritySafety lockout
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: no - the fault remains displayed until the cause is eliminated.

Manual reset: yes - by a competent person, who eliminates the fault and resets the internal circuit breaker (operating instructions).

On the flexoTHERM exclusive (VWF ../4)

Does the heat pump stop?Yes
SeveritySafety lockout
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: no - the fault remains displayed until the cause is eliminated.

Manual reset: yes - by a competent person who resets the internal circuit breaker (operating instructions).

What you can check

  • Note the full code and text shown on the display (and the date/time it appeared). Check the heat pump supply breaker/isolator (and back-up heater breaker, if separate) at the consumer unit is on; if a breaker has tripped more than once, leave it off and call an engineer - do not open any casing. Tell your installer: the back-up heater's safety device must be investigated and reset by a competent person.

What the engineer will check

On the aroTHERM plus (VWL ../6 A)

  • Check the electric back-up heater and its supply, reset the internal circuit breaker, check electrical connections and measure supply voltage (fault list per flexoTHERM table for the same code).

Who to ask for: Heat pump engineer with electrical competence (qualified electrician for supply/phase faults).

Certification: Competent electrician (BS 7671 / Part P) for supply-side work.

On the flexoTHERM exclusive (VWF ../4)

  • Check the electric back-up heater and its power supply, and reset the circuit breaker; Check the electrical connections; Measure the voltage at the electrical connection for the electric back-up heater.

Who to ask for: Heat pump engineer with electrical competence (qualified electrician for supply/phase faults).

Certification: Competent electrician (BS 7671 / Part P) for supply-side work.

What you might notice

What owners and engineers report

11 owner and engineer reports mention this.

  • No hot water on the aroTHERM plus (VWL ../6 A): 5 reports
  • Hot water not hot enough on the aroTHERM plus (VWL ../6 A): 3 reports
  • Insufficient heating (house not warm enough) on the aroTHERM plus (VWL ../6 A): 3 reports

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026