SolarpunkHomes
Sign inCall us · +44 7510 081687
Heat pumps
Heat pumps · Error codes · Vaillant
27Vaillant · geoTHERM (VWS/VWW ../2, VWS ../3)

27 on a Vaillant geoTHERM: Coolant (refrigerant) pressure too high - high pressure switch tripped (30 bar g)

Short answer

On a Vaillant heat pump, 27 means: Coolant (refrigerant) pressure too high - high pressure switch tripped (30 bar g). The heat pump keeps running with some functions stopped. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Coolant (refrigerant) pressure too high - high pressure switch tripped (30 bar g).

Part involved: Coolant.

When it shows: Temporary shutdown: compressor stops, heat pump remains in operation; becomes a fault-induced shutdown (60/62/81/83/84) if it occurs three times in a row.

Likely causes:

  • Heat consumer side using too little heat: air in heating system; heating pump defective/low output; no low-loss header/buffer; buffer sensors VF1/RF1 swapped; underfloor room controllers closing; DHW cylinder too small; dirt strainers clogged; stop valves closed; TEV incorrectly adjusted/defective.

Is it safe?

Does the heat pump stop?Partly
SeverityFault — clears by itself when the condition goes
Engineer needed?Yes

The heat pump keeps running with some functions stopped.

Resetting itself: yes - compressor restarts automatically after 5 min (60 min after errors 27/29) once the cause is removed.

Manual reset: not required.

What you can check

  • Note the full code and text shown on the display (and the date/time it appeared). The geoTHERM operating manual says: do not attempt to remove the source of the malfunction yourself; only an expert technician can remedy the fault and reset the error code. Warnings (26, 36) and temporary faults can be noted and discussed at the next inspection.

What the engineer will check

  • Bleed heating system; check pump; check system hydraulics and sensor positions; clean strainers; open stop valves; check refrigerant circuit (restart after 60 min earliest).

Who to ask for: F-gas certified refrigeration engineer with heat pump experience (R290 flammable-refrigerant competence required for aroTHERM plus / GeniaAir).

Certification: F-gas Category I (Regulation (EU) 517/2014 as retained in GB) certificate; flammable (R290) refrigerant training for R290 units.

What you might notice

What owners and engineers report

1 owner and engineer report mentions this.

  • No heating on the geoTHERM (VWS/VWW ../2, VWS ../3): 1 report

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026