E008Rinnai

E008 on a Rinnai heat pump: Compressor driver limitation alarm

Short answer

On a Rinnai heat pump, E008 means: Compressor driver limitation alarm. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 24 September 2026 · 2 sources

What it means

On the HPI (HPi32) R32 monobloc

The manual says: Compressor driver limitation alarm.

Part involved: compressor inverter drive board.

When it shows: Compressor fails to reach ramp speed within 30 min.

On the R290 monobloc (HPR290)

The manual says: Forced compressor shutdown for luck of lubrication.

Part involved: compressor / refrigerant circuit.

When it shows: Compressor fails to reach ramp speed within 30 min.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — clears by itself when the condition goes
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: unknown.

Manual reset: manual after 3 trips per hour.

What you can check

  • Note the code shown on the controller and the model number on the unit's rating label before contacting your installer.
  • Check that the heat pump's isolator and consumer-unit breaker are on; do not open any casing.

What the engineer will check

On the HPI (HPi32) R32 monobloc

  • Check supply voltage and phase at the unit terminals.
  • Check compressor U/V/W connections and compressor winding resistance.
  • Check drive board heatsink cooling and fan.
  • Replace the inverter/driver board if faults persist.

Who to ask for: Heat pump engineer.

Certification: Heat pump installer competence; F-gas and flammable-refrigerant (R32/R290) handling competence for any refrigerant-circuit work.

On the R290 monobloc (HPR290)

  • Record high/low pressures, discharge/suction temperatures and EEV steps with the unit running.
  • Check water-side flow and air-side coil (blocked/frosted fins).
  • Check pressure switches/transducers and wiring.
  • Leak-test the refrigerant circuit and correct the charge (F-gas / flammable-refrigerant competent engineer only).

Who to ask for: Heat pump engineer.

Certification: Heat pump installer competence; F-gas and flammable-refrigerant (R32/R290) handling competence for any refrigerant-circuit work.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 24 September 2026