H90Panasonic · Panasonic, all models

H90 on a Panasonic heat pump: Indoor/outdoor abnormal communication

Short answer

On a Panasonic heat pump, H90 means: Indoor/outdoor abnormal communication. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Indoor/outdoor abnormal communication.

Part involved: Indoor-outdoor connection cable; indoor/outdoor PCB.

When it shows: During operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Service-manual table judgement: > 1 min after starting operation (L, K, J MDC, J MXC, J AIO, H, F, E, D5, D8, C).

Likely causes:

  • 1 Faulty outdoor unit PCB (main). 2 Faulty indoor unit PCB (main). 3 Indoor-outdoor signal transmiss ion error due to wrong wiring. 4 Indoor-outdoor signal transmission error due to breaking of w ire in the connection wires between the indoor and outdoor units. 5 Indoor-outdoor signal transmiss ion error due to disturbed power supply waveform.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated in the Panasonic documents opened; protection counters lock out after the stated number of occurrences.

Manual reset: User: 'Error Reset' in the remote-controller Quick Menu (H/J/K/L controllers) or OFF/ON; engineer must clear the underlying cause (service manuals: 'When error happens, the power has to be reset').

What you can check

  • Read and note the code shown blinking on the remote controller (also stored under System Check > Error history). Per the Panasonic operating instructions the user may switch the system OFF/ON at the remote controller and use 'Error Reset' in the Quick Menu; if the code returns, leave the system and contact the installer (UK user guide lists Panasonic technical support as the fallback). Check the heat pump circuit breaker(s)/isolator at the consumer unit are ON (a tripped breaker is listed in the operating instructions' checks); if a breaker keeps tripping, leave it off and call an engineer.

What the engineer will check

  • Check outdoor unit supply and isolator; check indoor/outdoor interconnecting cable for wrong wiring or breaks; check supply waveform; check indoor and outdoor PCBs.

Who to ask for: Heat pump engineer with electrical competence.

Certification: Electrical work to BS 7671 by a competent person; F-gas certification if the refrigerant circuit is opened.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.