SolarpunkHomes
Sign inCall us · +44 7510 081687
Heat pumps
Heat pumps · Error codes · Panasonic
F15Panasonic · Panasonic, all models

F15 on a Panasonic heat pump: Outdoor fan motor lock abnormality

Short answer

On a Panasonic heat pump, F15 means: Outdoor fan motor lock abnormality. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Outdoor fan motor lock abnormality.

Part involved: Outdoor fan motor (DC); outdoor PCB.

When it shows: The rotation speed detected by the Hall IC of the fan motor during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550 rpm or < 50 rpm). Service-manual table judgement: 2 times occurrence within 30 minutes (L, K, J MDC, J MXC, J AIO, H, F, E, D5, D8, C).

Likely causes:

  • 1 Operation stop due to short cir cuit inside the fan motor winding. 2 Operation stop due to breaking of wire inside the fan motor. 3 Operation stop due to break ing of fan motor lead wires. 4 Operation stop due to fan motor Hall IC malfunction. 5 Operation error due to faulty outdoor unit PCB.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: Not stated in the Panasonic documents opened; protection counters lock out after the stated number of occurrences.

Manual reset: User: 'Error Reset' in the remote-controller Quick Menu (H/J/K/L controllers) or OFF/ON; engineer must clear the underlying cause (service manuals: 'When error happens, the power has to be reset').

What you can check

  • Read and note the code shown blinking on the remote controller (also stored under System Check > Error history). Per the Panasonic operating instructions the user may switch the system OFF/ON at the remote controller and use 'Error Reset' in the Quick Menu; if the code returns, leave the system and contact the installer (UK user guide lists Panasonic technical support as the fallback). Check from a distance that the outdoor unit air inlet/outlet is not blocked by snow, leaves or other debris (listed in the operating instructions' checks before calling for service); never reach into the fan.

What the engineer will check

  • Isolate power; check fan blade for obstruction or ice; check fan motor winding, lead wires and Hall IC feedback (fault if >2550 rpm or <50 rpm); check outdoor PCB.

Who to ask for: Heat pump engineer with electrical competence.

Certification: Electrical work to BS 7671 by a competent person; F-gas certification if the refrigerant circuit is opened.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026