84 on a Hitachi heat pump: High water pressure

Short answer

On a Hitachi heat pump, 84 means: High water pressure. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: High water pressure.

Part involved: water pressure.

When it shows: Water pressure >= 3.7 bar at pressure sensor.

Likely causes:

  • Water pressure >= 3.6-3.7 bar measured by the pressure sensor.

Is it safe?

Switch the heat pump off at its isolator and call an engineer.

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: no.

Manual reset: Stop the unit (via unit controller / power off-on) after the cause is fixed.

What you can check

  • Read and note the alarm code and any retry code (e.g. P70) shown on the unit controller.
  • Check the heat pump supply breaker/isolator at the consumer unit is ON.
  • Check the pressure gauge reading and that the filling loop is closed (an open filling loop can over-pressurise the system); do not vent or drain the system yourself.
  • Call an engineer.

What the engineer will check

  • Follow SMGB0146 section 6.7 troubleshooting flowchart for alarm 84.
  • Check water pump operation and fuse, pump feedback.
  • Check all circuit valves open, clean strainers/filters (Filter+ valve).
  • Check water pressure > 1 bar, bleed air, check flow and pressure switch/sensor continuity.
  • Check heater contactors, water thermistors and minimum system water volume.

Who to ask for: Heating engineer / MCS heat pump installer.

Certification: G3 unvented qualification where a DHW cylinder is involved.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026