55Hitachi

55 on a Hitachi heat pump: Abnormality of inverter module (inverter non-operation)

Short answer

On a Hitachi heat pump, 55 means: Abnormality of inverter module (inverter non-operation). The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Abnormality of inverter module (inverter non-operation).

Part involved: inverter module.

Likely causes:

  • Failure of DIP-IPM, IPM or inverter PCB.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

No need to switch off — call an engineer if it comes back.

Resetting itself: no.

Manual reset: Stop the unit (via unit controller / power off-on) after the cause is fixed.

What you can check

  • Read and note the alarm code and any retry code (e.g. P70) shown on the unit controller.
  • Check the heat pump supply breaker/isolator at the consumer unit is ON.
  • Restart once via the unit controller (or switch off/on at the isolator) - the manual states the unit must be stopped to release most alarms; if the code returns, call an engineer.

What the engineer will check

  • Follow SMGB0146 section 6.7 troubleshooting flowchart for alarm 55.
  • Isolate power and wait for capacitor discharge before opening the electrical box.
  • Check inverter PCB, IPM/DIP-IPM, current sensor wiring and connectors.
  • Check compressor and fan motor windings; check heat exchanger for clogging.

Who to ask for: Heat pump service engineer (electrical/inverter diagnostics).

Certification: Competent electrical worker (BS 7671); isolate and wait 10 min for capacitor discharge.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026