27 on a Hitachi heat pump: Economizer thermistor abnormality

Short answer

On a Hitachi heat pump, 27 means: Economizer thermistor abnormality. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 2 sources

What it means

On the Yutaki M (RASM monobloc)

The manual says: Economizer thermistor abnormality.

Part involved: economizer thermistor.

When it shows: Thermistor < 0.2 kOhm (short) or open.

Likely causes:

  • Thermistor short-circuited (<0.2 kOhm) or open circuit.

On the Yutaki M (RHUE, 1st generation)

The manual says: Failure of discharge gas pressure sensor (open/short).

Is it safe?

On the Yutaki M (RASM monobloc)

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

No need to switch off — call an engineer if it comes back.

Resetting itself: no.

Manual reset: Stop the unit (via unit controller / power off-on) after the cause is fixed.

On the Yutaki M (RHUE, 1st generation)

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

No need to switch off — call an engineer if it comes back.

Resetting itself: unknown.

Manual reset: Power OFF/ON to remove alarms in Yutaki M and system controller (TCGB0090 p.141 for F16/F17).

What you can check

  • Read and note the alarm code and any retry code (e.g. P70) shown on the unit controller.
  • Check the heat pump supply breaker/isolator at the consumer unit is ON.
  • Restart once via the unit controller (or switch off/on at the isolator) - the manual states the unit must be stopped to release most alarms; if the code returns, call an engineer.

What the engineer will check

  • Follow SMGB0146 section 6.7 troubleshooting flowchart for alarm 27.
  • Check thermistor/sensor connector seating and wiring on the PCB.
  • Measure thermistor resistance against the characteristic table; replace sensor if out of range.
  • Replace PCB if sensor and wiring are good.

Who to ask for: Heat pump service engineer.

Certification: None specific (electrical competence for PCB work).

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026