SolarpunkHomes
Sign inCall us · +44 7510 081687
Heat pumps
Heat pumps · Error codes · Hitachi
23Hitachi

23 on a Hitachi heat pump: Failure of discharge gas temperature thermistor (open/short)

Short answer

On a Hitachi heat pump, 23 means: Failure of discharge gas temperature thermistor (open/short). The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause. The wording differs by model range — each is shown below.

Reviewed 23 September 2026 · 2 sources

What it means

On the Yutaki M (RHUE, 1st generation)

The manual says: Failure of discharge gas temperature thermistor (open/short).

On the Yutaki S80 (high-temperature cascade split)

The manual says: Abnormal operation of the thermistor for the discharge gas (Td) - Yutaki S80 R134a stage.

Part involved: S80 discharge gas thermistor (Td, THM9 at PCB).

Likely causes:

  • Loose, disconnected, broken or short-circuited connector.

Is it safe?

On the Yutaki M (RHUE, 1st generation)

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

No need to switch off — call an engineer if it comes back.

Resetting itself: unknown.

Manual reset: Power OFF/ON to remove alarms in Yutaki M and system controller (TCGB0090 p.141 for F16/F17).

On the Yutaki S80 (high-temperature cascade split)

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

No need to switch off — call an engineer if it comes back.

Resetting itself: no.

Manual reset: Stop the unit (via unit controller / power off-on) after the cause is fixed.

What you can check

  • Read and note the alarm code and any retry code (e.g. P70) shown on the unit controller.
  • Check the heat pump supply breaker/isolator at the consumer unit is ON.
  • Restart once via the unit controller (or switch off/on at the isolator) - the manual states the unit must be stopped to release most alarms; if the code returns, call an engineer.

What the engineer will check

  • Follow SMGB0146 section 6.7 troubleshooting flowchart for alarm 23.
  • Check thermistor/sensor connector seating and wiring on the PCB.
  • Measure thermistor resistance against the characteristic table; replace sensor if out of range.
  • Replace PCB if sensor and wiring are good.

Who to ask for: Heat pump service engineer.

Certification: None specific (electrical competence for PCB work).

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026