SolarpunkHomes
Sign inCall us · +44 7510 081687
Heat pumps
Heat pumps · Error codes · Hitachi
102Hitachi · Yutaki S80 (high-temperature cascade split)

102 on a Hitachi Yutaki S80: Activation of protection control for excessively high pressure (retry code P12)

Short answer

On a Hitachi heat pump, 102 means: Activation of protection control for excessively high pressure (retry code P12). The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Activation of protection control for excessively high pressure (retry code P12).

Part involved: S80 R134a discharge pressure.

When it shows: Pd >= 2.78 MPa for 10 s after P12 retry.

Likely causes:

  • Stop after P12 retry due to discharge pressure Pd >= 2.78 MPa for 10 s.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

No need to switch off — call an engineer if it comes back.

Resetting itself: retry then stop.

Manual reset: Stop the unit (via unit controller / power off-on) after the cause is fixed.

What you can check

  • Read and note the alarm code and any retry code (e.g. P70) shown on the unit controller.
  • Check the heat pump supply breaker/isolator at the consumer unit is ON.
  • Restart once via the unit controller (or switch off/on at the isolator) - the manual states the unit must be stopped to release most alarms; if the code returns, call an engineer.

What the engineer will check

  • Follow SMGB0146 section 6.7 troubleshooting flowchart for alarm 102.
  • Check refrigerant charge and for leaks (F-gas qualified).
  • Check expansion valve operation and strainers for clogging.
  • Check heat exchanger/fan for blockage, pressure and temperature sensors.
  • Check water flow (low flow causes high-pressure trips in heating).

Who to ask for: F-gas certified refrigeration / heat pump engineer (Hitachi Yutaki trained).

Certification: F-gas certificate (Category I); A2L (R32) flammable refrigerant training for R32 units.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.

Reviewed: 23 September 2026