Heat pumps · Error codes · Hitachi
02-91Hitachi · Yutaki M (RHUE, 1st generation)

02-91 on a Hitachi Yutaki M: Excessively high discharge gas temperature

Short answer

On a Hitachi heat pump, 02-91 means: Excessively high discharge gas temperature. The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Excessively high discharge gas temperature.

Is it safe?

Does the heat pump stop?Yes
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

No need to switch off — call an engineer if it comes back.

Resetting itself: unknown.

Manual reset: Power OFF/ON to remove alarms in Yutaki M and system controller (TCGB0090 p.141 for F16/F17).

What you can check

  • Read and note the alarm code and any retry code (e.g. P70) shown on the unit controller.
  • Check the heat pump supply breaker/isolator at the consumer unit is ON.
  • Restart once via the unit controller (or switch off/on at the isolator) - the manual states the unit must be stopped to release most alarms; if the code returns, call an engineer.

What the engineer will check

  • Follow SMGB0146 section 6.7 troubleshooting flowchart for alarm 02-91.
  • Check refrigerant charge and for leaks (F-gas qualified).
  • Check expansion valve operation and strainers for clogging.
  • Check heat exchanger/fan for blockage, pressure and temperature sensors.
  • Check water flow (low flow causes high-pressure trips in heating).

Who to ask for: F-gas certified refrigeration / heat pump engineer (Hitachi Yutaki trained).

Certification: F-gas certificate (Category I); A2L (R32) flammable refrigerant training for R32 units.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.