OU-A3 on a Fujitsu WATERSTAGE split: Compressor temperature protection (permanent stoppage)

Short answer

On a Fujitsu heat pump, OU-A3 means: Compressor temperature protection (permanent stoppage). The heat pump stops until the fault clears or is reset. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Compressor temperature protection (permanent stoppage).

Part involved: outdoor unit PCB/refrigerant circuit.

Likely causes:

  • Valve closed; EEV failure; gas leak / low charge; compressor thermistor failure; outdoor fan failure; outdoor heat exchanger clogged.

Is it safe?

Switch the heat pump off at its isolator and call an engineer.

Does the heat pump stop?Yes
SeveritySafety lockout
Engineer needed?Yes

The heat pump stops until the fault clears or is reset.

Resetting itself: no.

Manual reset: engineer (power cycle / clear on outdoor PCB).

What you can check

  • Note the error number shown after pressing the Info (i) key on the Waterstage user interface. Check the heat pump breakers/isolators are on. The hydraulic unit shows error 370; the specific code is shown by LED flashes on the hydraulic interface PCB / outdoor PCB, which only an engineer should access. Check the outdoor unit is not blocked by leaves, snow or ice (look only). If the unit repeatedly locks out, leave it off and call an engineer (possible refrigerant loss).

What the engineer will check

  • Per SHP maintenance manual 'Clear' procedure: Valve closed; EEV failure; gas leak / low charge; compressor thermistor failure; outdoor fan failure; outdoor heat exchanger clogged. Access outdoor PCB (ERROR LED, press ENTER to read flash count), check connectors, sensor resistances, supply voltage (198-264 V AC 1ph), serial signal (AC 70-130 V between terminals), valves/EEV, refrigerant charge (F-gas), fan motor, compressor windings, IPM/PFC boards.

Who to ask for: Heat pump / refrigeration engineer (manufacturer-trained).

Certification: F-gas certification for refrigerant-circuit work; electrical competence (Part P/18th Edition) for PCB/wiring.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.