E041CTC · control system alarm/information platform (error-code grouping)

E041 on a CTC control system alarm/information platform: Low brine temp: incoming brine temperature from borehole/ground loop too low; cold side dimensioning should be checked

Short answer

On a CTC heat pump, E041 means: Low brine temp: incoming brine temperature from borehole/ground loop too low; cold side dimensioning should be checked. The heat pump keeps running with some functions stopped. An engineer is needed to fix the cause.

Reviewed 23 September 2026 · 1 source

What it means

The manual says: Low brine temp: incoming brine temperature from borehole/ground loop too low; cold side dimensioning should be checked.

Part involved: brine circuit.

Likely causes:

  • Incoming brine temperature too low - cold side under-dimensioned.

Is it safe?

Does the heat pump stop?Partly
SeverityFault — needs a manual reset once the cause is fixed
Engineer needed?Yes

The heat pump keeps running with some functions stopped.

Manual reset: Press "Reset alarm" on the display; a persisting fault must be rectified before it can be reset.

What you can check

  • If the manual instruction applies, press "Reset alarm" on the display once and note whether the alarm returns (manual allows reset and re-check).
  • Note the alarm code/text, the product model and serial number and contact your installer.

What the engineer will check

  • Bleed the brine circuit.
  • Check brine pump speed setting and brine filter.
  • Check collector length/dimensioning and brine temperatures.

Who to ask for: ground source heat pump.

What you might notice

Sources

A code explains what the controller detected, not a confirmed root cause.